ELE04-02368
| ELE-Aging Inspection | 4/26/2005 | 4/26/2005 | 4/26/2005 12:00:00 AM | | PASS |
|
|
ok to final 4/26/2005 4:20:28 PM
|
ELE04-02467
| ELE-Aging Inspection | 4/26/2005 | 4/26/2005 | 4/26/2005 12:00:00 AM | | PASS |
|
|
ok to final 4/26/2005 10:47:28 AM
|
ELE03-03039
| ELE-Aging Inspection | 4/26/2005 | 4/26/2005 | 4/26/2005 12:00:00 AM | | DONE |
|
|
still under construction. Will start partials in couple of weeks for finals 4/26/2005 10:24:57 AM
|
ELE05-01411
| Electrical Rough-In | 4/26/2005 | 4/26/2005 | 4/26/2005 12:00:00 AM | A | PASS |
|
|
ric ok
|
ELE05-01397
| Temporary Service | 4/22/2005 | 4/26/2005 | 4/26/2005 12:00:00 AM | A | PASS |
|
|
###-#### ALLAN t/s u/g n ok 4/26/2005 8:02:44 AM
|
ELE05-01410
| Rough-In Permanent Service | 4/25/2005 | 4/26/2005 | 4/26/2005 12:00:00 AM | A | PASS |
|
|
dean ###-#### ric ok p/s u/g n ok 4/26/2005 8:59:30 AM
|
ELE05-01411
| Rough-In Permanent Service | 4/25/2005 | 4/26/2005 | 4/26/2005 12:00:00 AM | A | CANC |
|
|
dean ###-#### p/s not ready 4/26/2005 8:57:18 AM
|
ELE05-01290
| Final | 4/25/2005 | 4/26/2005 | 4/26/2005 12:00:00 AM | A | FAIL |
|
|
Please meet Brian (###-####) at 7:30 am. He will have a ladder to access the roof. Thank you!; Phone #: ###-#### Internet Inspection Request from: Tawnya McKinney met contr, left corr notice,110.26(A),(B),access,and working space and depth shall be provided for. 250.122(A) equipment ground shall be min #8 copper 4/26/2005 8:08:45 AM
|
ELE05-01383
| Rough-In Permanent Service | 4/25/2005 | 4/26/2005 | 4/26/2005 12:00:00 AM | A | PASS |
|
|
Internet Inspection Request from: Bob Glenn called contr about 334.80 more than 2 wires in hole to be foam sealed. ric ok, p/s u/g n ok 4/26/2005 8:29:58 AM
|
ELE05-01127
| Electrical Rough-In | 4/25/2005 | 4/26/2005 | 4/26/2005 12:00:00 AM | A | FAIL |
|
|
need potting inspection on pool Internet Inspection Request from: Andy Rose pool 1/2 full of water, called contr, left do not cover sticker 4/26/2005 9:29:02 AM
|
ELE04-02595
| Final | 4/25/2005 | 4/26/2005 | 4/26/2005 12:00:00 AM | A | NR |
|
|
Scheduled by a contractor via Hello! on 4/25/2005 at 4:48:26 PM. Contact: ###-####. wanted ri only, see added insp 4/26/2005 10:49:24 AM
|
ELE04-02595
| Electrical Rough-In | 4/26/2005 | 4/26/2005 | 4/26/2005 12:00:00 AM | A | PASS |
|
|
clg cover ok 1st floor corridor, meeting rooms, offices
|
ELE05-01277
| Electrical Rough-In | 4/26/2005 | 4/26/2005 | 4/26/2005 12:00:00 AM | P | PASS |
|
|
ceiling inspection please///bob; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok to cover clg 4/26/2005 1:46:21 PM
|
ELE05-00224
| Final | 4/26/2005 | 4/26/2005 | 4/26/2005 12:00:00 AM | P | PASS |
|
|
can you SIGN this off yet? ok to final 4/26/2005 4:19:35 PM
|
ELE05-01127
| Electrical Rough-In | 4/26/2005 | 4/26/2005 | 4/26/2005 12:00:00 AM | P | PASS |
|
|
potting ispection on pool Internet Inspection Request from: Andy Rose potting ok 4/26/2005 2:26:17 PM
|
ELE04-02196
| Final | 4/26/2005 | 4/26/2005 | 4/26/2005 12:00:00 AM | P | PASS |
|
|
todd hall ###-#### called contr. ok to final 4/26/2005 12:37:40 PM
|