Inspections for the day of: Wednesday, April 26, 2006.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01416 Temporary Service4/26/20064/26/20064/26/2006 4:00:54 PMPPASS
t/s u/g n ok
ELE06-00238 Final4/26/20064/26/20064/26/2006 3:05:50 PMPPASS
looked at sign, ok to final
ELE06-01417 Temporary Service4/26/20064/26/20064/26/2006 2:21:19 PMPPASS
t/s u/g n ok
ELE06-01438 Electrical Rough-In4/25/20064/26/20064/26/2006 11:49:56 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr, left corr notice front door, nec 300.4(A)&(D) edge of holes and mc cable shall be 1 1/4" from edge of framing member, 330.30(B) mc cable shall be supported within 12" of box, 358.30(A) emt shall be supported within 3' of box, 110.12(A) unused openings shall be closed, BCC all make-up shall be done, mud rings installed, mc cable in boxes
ELE06-01432 Temporary Service4/25/20064/26/20064/26/2006 9:53:37 AMAPASS
###-#### t/s u/g n ok
ELE06-01407 Rough-In Permanent Service4/25/20064/26/20064/26/2006 9:40:02 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr to id brkrs, check outlet space up bedroom in 9635, ric ok p/s u/g n ok
ELE06-01367 Rough-In Permanent Service4/24/20064/26/20064/26/2006 8:58:57 AMAPASS
Scheduled by a contractor via Hello! on 4/24/2006 at 8:00:11 AM. Contact: ###-####. ric ok, p/s u/g n ok
ELE06-01366 Rough-In Permanent Service4/25/20064/26/20064/26/2006 8:36:34 AMAPASS
Scheduled by a contractor via Hello! on 4/25/2006 at 6:28:37 AM. Contact: ###-####. ric ok, p/s u/g n ok
ELE06-01427 Permanent Service4/25/20064/26/20064/25/2006 10:19:39 AMACANC
Hooked up generator; new service switch; grounding; new automatic transfer switch.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs Inspection cancelled from web by: Kathy Briggs