Inspections for the day of: Thursday, April 26, 2007.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00765 FIR-Aging Inspection4/26/20074/26/20075/1/2007 12:31:55 PM DEFR
BLD06-01142 FIRE-Final Inspection4/26/20074/26/20074/26/2007 5:45:54 PMPPART
Okay for temp occ. per agreement with the fire dept.
BLD06-01141 FIRE-Final Inspection4/26/20074/26/20074/26/2007 5:45:05 PMPPART
Okay for temp occ. per agreement with the fire dept.
BLD06-01140 FIRE-Final Inspection4/26/20074/26/20074/26/2007 5:44:15 PMPPART
Okay for temp occ. per agreement with the fire dept.
BLD06-01139 FIRE-Final Inspection4/26/20074/26/20074/26/2007 5:43:23 PMPPART
Okay for temp occ. per agreement with the fire dept.
BLD06-01137 FIRE-Final Inspection4/26/20074/26/20074/26/2007 5:42:35 PMPPART
Okay for temp occ. per agreement with the fire dept.
BLD06-01135 FIRE-Final Inspection4/26/20074/26/20074/26/2007 5:41:48 PMPPART
Okay for temp occ. per agreement with the fire dept.
FIR06-00495 INSP-Final Inspection4/25/20074/26/20074/26/2007 5:40:04 PMAPART
Tested 120V smoke alarms for the dwelling units on the 5th, 4th, 3rd and 2nd floors, noted one device to be moved in unit 210, one device repaired while on site 3rd floor, no access to unit 312, verified signals recieved and corrected descriptor for the waterflow alarms.
FIR07-00231 INSP-Sprinkler Rough-in4/25/20074/26/20074/26/2007 5:35:42 PMAPASS
Corrections verified for compliance, OH rough-in is okay for cover at the drop ceilings.
BLD06-02798 FIRE-Final Inspection4/25/20074/26/20074/26/2007 2:30:50 PMPPASS
Life safety inspeciton passed, noted manual flush bolts at the inactive leaf on the double doors from the confrence room are not allowed.
BLD05-00978 FIRE-Final Inspection4/25/20074/26/20074/26/2007 2:26:31 PMPPASS
Items on correction notice have been completed, final fire life safety inspection passed.
BLD07-00470 FIRE-Final Inspection4/26/20074/26/20074/26/2007 1:23:06 PMPPASS
Life safety inspection passed.
FIR07-00034 INSP-Sprinkler Rough-in4/25/20074/26/20074/26/2007 1:14:31 PMAPART
Inspection for the 3rd floor rough-in is approved except as noted on stamped plans, overspaced heads above the west stairway, riser nipple at the SE corner, missing guage at the top west stairway standpipe hose connection.
BLD06-00205 FIRE-Final Inspection4/26/20074/26/20074/26/2007 12:38:54 PMAPART
Need to complete related project permits pending completion of remodel work areas including the autology room for fire sprinkler and fire alarm as indicated on permit scope.
FIR07-00254 INSP-Final Inspection4/25/20074/26/20074/26/2007 12:36:49 PMAPASS
Final fire sprinkler inspection passed, all required corrections have been finished, permit finaled.
BLD07-00156 FIRE-Final Inspection4/26/20074/26/20074/26/2007 12:35:45 PMAPASS
Corrections verified for compliance, life safety inspection passed.
BLD06-03151 FIRE-Final Inspection4/25/20074/26/20074/26/2007 12:33:41 PMAPASS
Correction notice is complete, fire life safety passed.