Inspections for the day of: Thursday, April 26, 2007.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00941 INSP-Final Inspection4/25/20074/26/20074/27/2007 2:22:22 PMAFAIL
Per Brian the tamper switchs need adjusting so that a correct signal is given at the fire alarm panel
FIR06-00591 INSP-Final Inspection4/26/20074/26/20074/27/2007 2:20:30 PMPPASS
permit finaled
FIR06-00918 INSP-Final Inspection4/25/20074/26/20074/27/2007 2:18:39 PMAFAIL
Per Brian the fire alarm system has not been pre tested, there are multiple problems and the entire system needs to be tested from the beginning.
FIR07-00370 INSP-Final Inspection4/26/20074/26/20074/27/2007 1:25:30 PMPPASS
permit finaled per Brian
FIR06-00941 INSP-Sprinkler Rough-in/Hydro4/25/20074/26/20074/27/2007 11:58:18 AMAPASS
The hydro on the fire pump loop passed. It took two times per Brian.
FIR05-00536 INSP-Sprinkler Rough-in4/25/20074/26/20074/27/2007 11:09:59 AMACANC
Inspection is to be rescheduled
FIR06-00597 INSP-Final Inspection4/25/20074/26/20074/26/2007 12:00:13 PMAPASS
permit finaled
FIR07-00079 INSP-Supply line flush4/25/20074/26/20074/26/2007 11:14:45 AMAPASS
The underground flush passed
BLD06-02841 FIRE-Final Inspection4/25/20074/26/20074/26/2007 10:47:34 AMAFAIL
Need fire lane signage as discussed, remaining door hardware installed, test exit signs and emergency lights and either install duct detectors correctly with remote annunciators or remove since the units are less than 2,000cfm and do not share a common duct or return plenum
BLD06-01654 FIRE-Final Inspection4/25/20074/26/20074/26/2007 10:32:24 AMAFAIL
Provide correct sticker at the main exit, either remove the duct smoke detectors since they are not required or install correctly and provide with remote annunciators, provide asbuilt drawings for the relocation of the fire hydrant to city of boise, provide exit discharge lighting and provide correct door hardware on the north office door (remove the manual flush bolt)
FIR07-00314 INSP-Sprinkler Rough-in/Hydro4/25/20074/26/20074/26/2007 9:43:15 AMAPASS
Need paper taken off of two uprights along the exterior wall, need the annual inspection for the sprinkler system done and it appears the riser room has no sprinkler protection. I contacted jim danes about the items. Sprinkler piping is ok to cover.
FIR06-00466 INSP-Final Inspection4/25/20074/26/20074/26/2007 9:21:59 AMAFAIL
I inspected the second floor a/v's for operation. I also inspected the additional strobes added in the storage areas. See the original correction notice for items remaining that need inspection.
BLD06-03284 FIRE-Conference4/25/20074/26/20074/26/2007 9:20:29 AMAPASS
I went over life safety requirements with the general contractor
FIR02-00466 INSP-Final Inspection4/25/20074/26/20074/26/2007 8:07:17 AMAPASS
permit finaled
BLD06-00453 FIRE-Final Inspection4/25/20074/26/20074/26/2007 12:00:00 AMPCANC
dan - fire life safety - late afternoon ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
BLD06-00454 FIRE-Final Inspection4/25/20074/26/20074/26/2007 12:00:00 AMPCANC
dan - fire life safety - late afternoon ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith