Inspections for the day of: Monday, April 26, 2010.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-00502 Final4/26/20104/26/20104/26/2010 4:01:35 PMPPASS
warren Phone #: ###-#### ok to final, will install rest of receptacles for roof-top at next phase, no esc this project
ELE07-03222 Final4/23/20104/26/20104/26/2010 3:30:16 PMACANC
Call Terry first he has questions on outlet requirements ###-#### called, left message, contractor did not call this in
ELE10-00125 Final4/26/20104/26/20104/26/2010 3:27:47 PMPFAIL
Inspection requested from web by: Justin Frates called, left correction notice, NEC 210.52(A)(2) shall provide receptacle under bar/counter, 406.4 all receptacles shall be securely mounted, 406.4(D) receptacle face shall be flush with or project from cover, 406.5 receptacle covers shall be installed, 110.3 receptacles in laundry room shall operate, shall provide 12"x34" access in tub for maintenance, 410.2 shall provide clearance for closet fixture- purple room, BCC shall install trim for fixtures over desk, NOTE corrections shall be made within 5 working days or further action will be taken such as removal of power
ELE10-00871 Electrical Rough-In4/26/20104/26/20104/26/2010 2:25:42 PMPPASS
paul Phone #: ###-#### called, ric ok, no esc
ELE10-00675 Final4/26/20104/26/20104/26/2010 1:37:43 PMPPASS
Inspection requested from web by: Dan Rohl Phone #: ###-#### ok to final, no esc this project
ELE10-00702 Final4/26/20104/26/20104/26/2010 12:44:43 PMPCANC
see p/s
ELE10-00702 Permanent Service4/26/20104/26/20104/26/2010 12:44:17 PMPPASS
p/s u/g n ok , no esc this project
ELE09-02355 Final4/26/20104/26/20104/26/2010 12:43:11 PMPPASS
Pat Phone #: ###-#### ok to final, no esc
ELE10-00702 Final4/23/20104/26/20104/26/2010 12:22:04 PMAPASS
russ Phone #: ###-#### p/s u/g n ok, no esc this project
ELE10-00847 Rough-In Permanent Service4/26/20104/26/20104/26/2010 10:45:36 AMACANC
Uefer in crawl space Inspection requested from web by: Therrin Robertson Phone #: ###-#### see ri and p/s
ELE10-00847 Electrical Rough-In4/26/20104/26/20104/26/2010 10:45:27 AMAFAIL
Uefer in crawl space Inspection requested from web by: Therrin Robertson Phone #: ###-#### called, left correction notice, NEC 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 210.52(D) shall provide recptacle within 3' of bath sink, 210.52(H) shall provide receptacle in 10' hall, 362.30(A) shall strap ent within 3' of box, 334.30 shall not staple nm on edge, 334.23 shall protect cable within 6' of attc access, BCC shall provide box to terminate nm cable, NOTE corrections shall be made within 5 working days
ELE10-00847 Permanent Service4/26/20104/26/20104/26/2010 10:10:36 AMAPASS
Uefer in crawl space Inspection requested from web by: Therrin Robertson Phone #: ###-#### p/s u/g n ok
ELE09-01861 Final4/21/20104/26/20104/26/2010 9:47:41 AMAPASS
Jared Phone #: ###-#### corrections made, ok to final
ELE10-00629 Rough-In Permanent Service4/26/20104/26/20104/26/2010 9:31:22 AMAPASS
Inspection requested from web by: Roy Kay Phone #: ###-#### called about re-bar to be protected for concrete encased lectrode, ric ok, p/s o/h n ok
ELE10-00806 Electrical Rough-In4/23/20104/26/20104/26/2010 9:16:30 AMAPASS
wall rough-in Inspection requested from web by: jon gleason Phone #: ###-#### walls only ok to cover, no esc
ELE10-00868 Rough-In Permanent Service4/23/20104/26/20104/26/2010 8:53:56 AMACANC
Dino Phone #: ###-#### see ri and p/s
ELE10-00868 Electrical Rough-In4/26/20104/26/20104/26/2010 8:53:40 AMAFAIL
Dino Phone #: ###-#### called, left correction notice, NEC 210.52(A)(2) shall provide receptacles in 2' wall space in front room and patio entry, 334.23 shall protect cables at attic access in garage, 210.52(E) (1) shall provide receptacle at back of dwelling, NOTE corrections shall be made within 5 working days
ELE10-00868 Permanent Service4/26/20104/26/20104/26/2010 8:44:10 AMAPASS
Dino Phone #: ###-#### p/s u/g n ok
ELE10-00125 Final4/23/20104/26/20104/26/2010 8:20:03 AMANH
The tub upstairs will have a caulked removable tile to access the pump. Inspection requested from web by: Justin Frates Phone #: ###-#### called, nh, told to reschedule, fee due, left card