Inspections for the day of: Monday, April 26, 2010.
Number of inspections: 1
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorStephanie L. Cobbley
TitleFIRE ALARM PLAN REVIEWER
Phone #433-5610
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00551 INSP-Alarm Testing4/23/20104/26/20104/26/2010 5:40:42 PMAFAIL
All pull stations have been mounted too high and need to be relocated. The smoke detector above the panel is too high and needs to either be relocated or removed (it is not required in a fully sprinklered building). A notification device needs to be added to the hallway between the reception area and the kennels. An over-spaced notification device in the Salon needs to be relocated. There was no canned smoke available to test the duct detectors. None of the pull stations were tested at this inspection. All other notification device locations and functions were verified. Other signals tested and verified at this inspection were: the sprinkler tampers and flows, the loss of power for the main FACP as well as the remote power supplies, and the loss of phone lines.