BLD12-00678
| FIRE-Final Inspection | 4/26/2013 | 4/26/2013 | 4/26/2013 3:51:59 PM | P | PASS |
|
|
Smoke alarms have been added and tested. Life safety passed.
|
FIR13-00058
| INSP-Final Inspection | 4/26/2013 | 4/26/2013 | 4/26/2013 3:39:12 PM | P | FAIL |
|
|
Todays inspection request was just for a walk through to verify spacing/layout of the devices that have been installed. See the city approved plans for acouple of locations where corrections are needed. I deferred approval of the smoke detectors located in the sky lights to the fire dept. since they exceed 12" from the deck. Clay Freinwald Phone #: ###-####
|
BLD12-00382
| FIRE-Conference | 4/26/2013 | 4/26/2013 | 4/26/2013 3:03:29 PM | P | DONE |
|
|
I forwarded an email to mike with steed construction stating the code sections, IFC 907.4, where the smoke detectors being utilized for door release are required to be connected to the fire alarm system. This is in reference to the door at the bottom of the stairs from the mezzanine.
|
BLD12-01035
| FIRE-Conference | 4/26/2013 | 4/26/2013 | 4/26/2013 2:28:02 PM | P | DONE |
|
|
The fire dept access for this project does not match the approved plans. Scott and I discussed modifying the fire dept. access for existing conditions and it was approved with the condition that Brent, the owner, is to provide a modified plans showing the fenced yard enclosure, the tent structor and no access into the property from the south entrance.
|
BLD12-03180
| FIRE-Final Inspection | 4/24/2013 | 4/26/2013 | 4/26/2013 2:17:21 PM | P | PASS |
|
|
life safety passed
|
FIR13-00032
| INSP-Final Inspection | 4/25/2013 | 4/26/2013 | 4/26/2013 1:30:44 PM | P | PASS |
|
|
permit finaled
|
FIR12-00363
| FIR-Aging Inspection | 4/26/2013 | 4/26/2013 | 4/26/2013 11:13:48 AM | | NR |
|
|
Work is in progress
|
FIR12-00693
| INSP-Sprinkler Rough-in | 4/25/2013 | 4/26/2013 | 4/26/2013 11:12:12 AM | A | PASS |
|
|
Another residence is ok to cover. See sticker on window.
|
FIR12-00749
| INSP-Final Inspection | 4/25/2013 | 4/26/2013 | 4/26/2013 10:28:31 AM | A | PASS |
|
|
permit finaled
|
FIR13-00100
| INSP-Final Inspection | 4/23/2013 | 4/26/2013 | 4/26/2013 10:19:54 AM | A | FAIL |
|
|
Wire the duct smoke detectors to shut down the hvac units immediatley per IMC, resend signals for the tamper switches to verify "supervisory" signals are sent to central station and provide map and close out documents.
|
BLD12-02195
| FIRE-Final Inspection | 4/26/2013 | 4/26/2013 | 4/26/2013 12:00:00 AM | P | CANC |
|
|
Dillon Phone #: ###-#### -- cancelled per Dillon 4/26/13 @ 12:16, I called Troy and told him insp was cancelled//leg
|