FIR16-00210
| INSP-Sprinkler Rough-in/Hydro | 4/20/2016 | 4/26/2016 | 4/26/2016 3:53:06 PM | P | PASS |
|
|
Rough in inspection for standpipe complete, approved for cover. 200 psi hydrostatic test for standpipe passed/complete.
|
FIR15-00709
| INSP-Sprinkler Rough-in | 4/25/2016 | 4/26/2016 | 4/26/2016 3:19:45 PM | P | PASS |
|
|
Rough to cover inspection complete for overhead fire sprinkler piping on 1st and 2nd floor hardlids, 1st and 2nd floor hardlids approved for cover.
|
FIR16-00278
| INSP-Sprinkler Rough-in | 4/26/2016 | 4/26/2016 | 4/26/2016 2:33:09 PM | P | PART |
|
|
Rough to cover inspection complete for hardlids, overhead fire sprinkler piping above hardlids approved for cover.
|
BLD14-02705
| FIRE-Final Inspection | 4/26/2016 | 4/26/2016 | 4/26/2016 2:29:06 PM | P | CANC |
|
|
Inspection request cancelled, FIR permit attached to this project is still in issued status. FIR permit needs to be in finaled status before life fire safety inspection can be performed.
|
FIR16-00234
| INSP-Sprinkler Rough-in | 4/26/2016 | 4/26/2016 | 4/26/2016 1:16:33 PM | P | FAIL |
|
|
Female restroom approved for cover, notated with red in on city approved plans heads that are okay to cover. First head in mens restroom not approved for cover, mens restroom sprinkler head scales at 9 foot off of wall on city approved drawings, sprinkler head is installed 10ft 5in off of wall, head needs to be relocated. 4X8 foot sheet of plywood is attached to ceiling joists above mens restroom, no upright protection for that area, combustible material needs to either be fire rated/treated, removed or upright protection installed for combustible material.
|
FIR16-00247
| INSP-Final Inspection | 4/25/2016 | 4/26/2016 | 4/26/2016 11:53:38 AM | P | FAIL |
|
|
Commercial hood suppression system is reporting to fire panel as a trouble, hood suppression system needs to report as general fire.
|
FIR16-00129
| INSP-Sprinkler Rough-in | 4/26/2016 | 4/26/2016 | 4/26/2016 10:19:59 AM | P | PART |
|
|
Notated area's approved to cover with blue highlighter on city approved drawings, heads in hardlids marked blue with highlighter approved for cover.
|
FIR16-00207
| INSP-Sprinkler Rough-in | 4/25/2016 | 4/26/2016 | 4/26/2016 9:45:21 AM | A | PASS |
|
|
Overhead fire sprinkler rough to cover inspection complete, tenant space approved for cover.
|
FIR16-00015
| INSP-Sprinkler Rough-in | 4/25/2016 | 4/26/2016 | 4/26/2016 9:20:08 AM | A | PASS |
|
|
Rough to cover inspection complete, overhead fire sprinkler piping approved for cover.
|
FIR16-00233
| INSP-Sprinkler Rough-in | 4/25/2016 | 4/26/2016 | 4/26/2016 8:20:12 AM | A | PASS |
|
|
Overhead fire sprinkler rough to cover inspection complete for hardlid, hardlid is approved for cover.
|
FIR16-00106
| INSP-Sprinkler Rough-in/Hydro | 4/20/2016 | 4/26/2016 | 4/26/2016 8:13:40 AM | P | CANC |
|
|
Please call Jake when you are heading out. Thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
FIR16-00017
| INSP-Sprinkler Rough-in/Hydro | 4/20/2016 | 4/26/2016 | 4/25/2016 11:12:18 AM | P | CANC |
|
|
Please call Jake when you are heading out. Thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|