Inspections for the day of: Tuesday, April 26, 2016.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00210 INSP-Sprinkler Rough-in/Hydro4/20/20164/26/20164/26/2016 3:53:06 PMPPASS
Rough in inspection for standpipe complete, approved for cover. 200 psi hydrostatic test for standpipe passed/complete.
FIR15-00709 INSP-Sprinkler Rough-in4/25/20164/26/20164/26/2016 3:19:45 PMPPASS
Rough to cover inspection complete for overhead fire sprinkler piping on 1st and 2nd floor hardlids, 1st and 2nd floor hardlids approved for cover.
FIR16-00278 INSP-Sprinkler Rough-in4/26/20164/26/20164/26/2016 2:33:09 PMPPART
Rough to cover inspection complete for hardlids, overhead fire sprinkler piping above hardlids approved for cover.
BLD14-02705 FIRE-Final Inspection4/26/20164/26/20164/26/2016 2:29:06 PMPCANC
Inspection request cancelled, FIR permit attached to this project is still in issued status. FIR permit needs to be in finaled status before life fire safety inspection can be performed.
FIR16-00234 INSP-Sprinkler Rough-in4/26/20164/26/20164/26/2016 1:16:33 PMPFAIL
Female restroom approved for cover, notated with red in on city approved plans heads that are okay to cover. First head in mens restroom not approved for cover, mens restroom sprinkler head scales at 9 foot off of wall on city approved drawings, sprinkler head is installed 10ft 5in off of wall, head needs to be relocated. 4X8 foot sheet of plywood is attached to ceiling joists above mens restroom, no upright protection for that area, combustible material needs to either be fire rated/treated, removed or upright protection installed for combustible material.
FIR16-00247 INSP-Final Inspection4/25/20164/26/20164/26/2016 11:53:38 AMPFAIL
Commercial hood suppression system is reporting to fire panel as a trouble, hood suppression system needs to report as general fire.
FIR16-00129 INSP-Sprinkler Rough-in4/26/20164/26/20164/26/2016 10:19:59 AMPPART
Notated area's approved to cover with blue highlighter on city approved drawings, heads in hardlids marked blue with highlighter approved for cover.
FIR16-00207 INSP-Sprinkler Rough-in4/25/20164/26/20164/26/2016 9:45:21 AMAPASS
Overhead fire sprinkler rough to cover inspection complete, tenant space approved for cover.
FIR16-00015 INSP-Sprinkler Rough-in4/25/20164/26/20164/26/2016 9:20:08 AMAPASS
Rough to cover inspection complete, overhead fire sprinkler piping approved for cover.
FIR16-00233 INSP-Sprinkler Rough-in4/25/20164/26/20164/26/2016 8:20:12 AMAPASS
Overhead fire sprinkler rough to cover inspection complete for hardlid, hardlid is approved for cover.
FIR16-00106 INSP-Sprinkler Rough-in/Hydro4/20/20164/26/20164/26/2016 8:13:40 AMPCANC
Please call Jake when you are heading out. Thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
FIR16-00017 INSP-Sprinkler Rough-in/Hydro4/20/20164/26/20164/25/2016 11:12:18 AMPCANC
Please call Jake when you are heading out. Thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello