FIR16-00811
| INSP-Supply line flush | 4/25/2017 | 4/26/2017 | 4/26/2017 2:37:59 PM | P | PASS |
|
|
Underground supply line flush passed
|
BLD16-02699
| FIRE-Final Inspection | 4/25/2017 | 4/26/2017 | 4/26/2017 2:37:29 PM | P | FAIL |
|
|
Provide small documents, provide fire dept approval of tanks and pumps, repair main exit discharge light and corridor emergency light, remove deadbolt from beer cooler, remove thumbturn deadbolt (keyed ok) from main exit and provide indicator and sticker, install address, test the emergency fuel shut offs
|
BLD17-00861
| FIRE-Final Inspection | 4/26/2017 | 4/26/2017 | 4/26/2017 1:19:38 PM | P | PASS |
|
|
life safety passed. Dan to repair the exit sign prior to building inspection
|
FIR17-00080
| INSP-Sprinkler Rough-in | 4/25/2017 | 4/26/2017 | 4/26/2017 12:14:42 PM | A | FAIL |
|
|
Todays inspection was for another area for cover. I stopped inspection when I found missing uprights in canopy and different heads installed in building. Plans need to be provided/submitted that show the actual heads installed. I gave the ok to cover in the previous area where upright have been removed and batt insulation provided.
|
FIR16-00588
| INSP-Final Inspection | 4/26/2017 | 4/26/2017 | 4/26/2017 10:23:16 AM | P | CANC |
|
|
George, inspection is ready this AM if you can make that work. Phone #: ###-####
|
BLD17-00032
| FIRE-Final Inspection | 4/25/2017 | 4/26/2017 | 4/26/2017 10:22:27 AM | A | PASS |
|
|
life safety passed. Plan review approval is still pending on the deletion of the gate hardware and exit sign in the cooler.
|
FIR16-00712
| INSP-Supply line flush | 4/25/2017 | 4/26/2017 | 4/26/2017 9:19:24 AM | P | PASS |
|
|
Underground flushed passed
|
FIR16-00712
| INSP-Sprinkler Rough-in/Hydro | 4/25/2017 | 4/26/2017 | 4/26/2017 9:18:50 AM | A | PASS |
|
|
Underground hydro test passed
|
BLD16-01092
| FIRE-Final Inspection | 4/25/2017 | 4/26/2017 | 4/26/2017 9:01:21 AM | A | FAIL |
|
|
Life safety will be ok to final when the project related fire sprinkler and fire alarm permits are passed.
|
FIR16-00454
| INSP-Final Inspection | 4/25/2017 | 4/26/2017 | 4/26/2017 9:00:43 AM | A | FAIL |
|
|
Started inspection but found that the elevator recall did not function and panel was constantly in Trouble due to people trying to fix things so I stopped the inspection. Will need to start from beginning. Need review comments.
|
FIR17-00086
| INSP-Sprinkler Rough-in | 4/25/2017 | 4/26/2017 | 4/26/2017 8:58:49 AM | A | PASS |
|
|
Rough-in passed. Piping can be covered. As-builts need sent to plan review
|