Inspections for the day of: Wednesday, April 26, 2017.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00811 INSP-Supply line flush4/25/20174/26/20174/26/2017 2:37:59 PMPPASS
Underground supply line flush passed
BLD16-02699 FIRE-Final Inspection4/25/20174/26/20174/26/2017 2:37:29 PMPFAIL
Provide small documents, provide fire dept approval of tanks and pumps, repair main exit discharge light and corridor emergency light, remove deadbolt from beer cooler, remove thumbturn deadbolt (keyed ok) from main exit and provide indicator and sticker, install address, test the emergency fuel shut offs
BLD17-00861 FIRE-Final Inspection4/26/20174/26/20174/26/2017 1:19:38 PMPPASS
life safety passed. Dan to repair the exit sign prior to building inspection
FIR17-00080 INSP-Sprinkler Rough-in4/25/20174/26/20174/26/2017 12:14:42 PMAFAIL
Todays inspection was for another area for cover. I stopped inspection when I found missing uprights in canopy and different heads installed in building. Plans need to be provided/submitted that show the actual heads installed. I gave the ok to cover in the previous area where upright have been removed and batt insulation provided.
FIR16-00588 INSP-Final Inspection4/26/20174/26/20174/26/2017 10:23:16 AMPCANC
George, inspection is ready this AM if you can make that work. Phone #: ###-####
BLD17-00032 FIRE-Final Inspection4/25/20174/26/20174/26/2017 10:22:27 AMAPASS
life safety passed. Plan review approval is still pending on the deletion of the gate hardware and exit sign in the cooler.
FIR16-00712 INSP-Supply line flush4/25/20174/26/20174/26/2017 9:19:24 AMPPASS
Underground flushed passed
FIR16-00712 INSP-Sprinkler Rough-in/Hydro4/25/20174/26/20174/26/2017 9:18:50 AMAPASS
Underground hydro test passed
BLD16-01092 FIRE-Final Inspection4/25/20174/26/20174/26/2017 9:01:21 AMAFAIL
Life safety will be ok to final when the project related fire sprinkler and fire alarm permits are passed.
FIR16-00454 INSP-Final Inspection4/25/20174/26/20174/26/2017 9:00:43 AMAFAIL
Started inspection but found that the elevator recall did not function and panel was constantly in Trouble due to people trying to fix things so I stopped the inspection. Will need to start from beginning. Need review comments.
FIR17-00086 INSP-Sprinkler Rough-in4/25/20174/26/20174/26/2017 8:58:49 AMAPASS
Rough-in passed. Piping can be covered. As-builts need sent to plan review