Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-01687 Final4/25/20194/26/20194/26/2019 3:29:14 PMPPASS
Please call prior to heading out Alta Arner ###-#### Phone #: ###-#### Inspection requested via web by Andrea Grigsby
- furnace ac coil co ok
MEC18-02908 Final4/26/20194/26/20194/26/2019 2:49:02 PMPPASS
furnace ac coil co ok
MEC19-01578 Final4/26/20194/26/20194/26/2019 2:26:11 PMPPASS
Thomas ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- furnace ac coil co ok
MEC19-01669 Final4/25/20194/26/20194/26/2019 1:37:33 PMPFAIL
Please call Aleks on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- need to see electrical permit issused for final
- furnace ac coil co ok
MEC19-01669 Pressure Test4/25/20194/26/20194/26/2019 1:36:20 PMPPASS
Please call Aleks on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- 20lb gas pressure test ok
- tagged meter location
MEC19-01684 Rough-in4/26/20194/26/20194/26/2019 1:17:03 PMPFAIL
Inspection requested via web by Floyd Floyd Peek
- condensate lines need nail plate protection installed
MEC19-01366 Final4/22/20194/26/20194/26/2019 12:26:05 PMANH
Please call homeowner prior to arrival; Don Robbins Phone #: ###-#### Inspection requested via web by Andrea Grigsby
- Called and talked with owner before showing up but no one answered the door
left notice on front door
MEC19-01652 Final4/24/20194/26/20194/26/2019 12:06:12 PMAFAIL
Please call Beau at ###-#### when in route. Phone #: ###-#### Inspection requested via web by Sabrina DeHority
- A/C breaker size needs to be a 35 amp max
MEC19-01700 Rough-in4/25/20194/26/20194/26/2019 11:46:49 AMAFAIL
PART Phone #: ###-#### Inspection requested via web by Oleg Chervak
- need nail plates dryer exhaust
-ducts need to be sealed
- dryer vents in attic need to be supported
- need nail plates in one location for line sets
- line sets in breeze way need some more fire caulk
MEC18-05532 Rough-in4/25/20194/26/20194/26/2019 11:45:56 AMAFAIL
PART Phone #: ###-#### Inspection requested via web by Oleg Chervak
- hvac duct work needs sealed
- one fresh air duct needs flex connected to rigid duct work
- line sets on 3rd floor need supported
MEC19-01535 Rough-in4/25/20194/26/20194/26/2019 10:55:52 AMAFAIL
rough in and pressure test. Thank You Phone #: ###-#### Inspection requested via web by Lynn Johnston
- supply trunk line needs seams duct sealed
- need to see access for unit in ceiling framed out
MEC19-01535 Pressure Test4/26/20194/26/20194/26/2019 10:55:17 AMAPASS
rough in and pressure test. Thank You Phone #: ###-#### Inspection requested via web by Lynn Johnston
- 20lb gas pressure test ok
- tagged meter location
MEC19-00931 Pressure Test4/26/20194/26/20194/26/2019 10:31:40 AMPPASS
MARK IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
- 60lb gas pressure test ok
MEC19-01707 Pressure Test4/25/20194/26/20194/26/2019 10:14:47 AMAFAIL
Inspection requested via web by Don Dowers
- 20 lb gas pressure test fail gauge was under 20lb
MEC19-01508 Rough-in4/25/20194/26/20194/26/2019 9:59:25 AMAFAIL
Call Jason @ ###-#### with any issues. Phone #: ###-#### Inspection requested via web by Angie Maguire
- need to see where access panels are going to be installed for the ERV/ furnace in the attic
-furnace vent from the basment to the 1st floor needs a nail plate
-flex upstairs needs an elbow installed
(flex is being smashed)
- need all exhaust fans tied in
- dryer vent on 1st floor is sticking out of the wall
MEC19-01508 Pressure Test4/25/20194/26/20194/26/2019 9:52:48 AMAPASS
Call Jason @ ###-#### with any issues. Phone #: ###-#### Inspection requested via web by Angie Maguire
- 20lb gas pressure test ok
1- 5lb flue pressure test ok
- tagged meter location
MEC18-04315 Mec-Aging Inspection4/26/20194/26/20194/26/2019 8:45:28 AM FAIL
This permit hasn't been active since it was issued. Please schedule inspection with homeowner if work is finished. Permit will expire by the next mechanical aging inspection if not active
MEC19-00931 Conference4/26/20194/26/20194/26/2019 8:43:39 AMADONE
Please go by and let the manager know the gas piping to the oven failed the pressure test, and ask them to please stop using the oven until it does pass.
- Talked with Craig one of the store directors and informed him that the gas pressure test on the new gas line for the oven didn't pass. And that the City of of Boise feels its best to quit using the ovens until the gas pressure test passes. Craig agreed with me and said he would stop the ovens and starting making phone calls to get this issue resolved.
MEC18-04308 Mec-Aging Inspection4/26/20194/26/20194/26/2019 8:16:27 AM FAIL
This permit has not been active since it was issued. Need to schedule inspection with homeowner if work is finished. Permit will expire at the next mechanical aging inspection if not active.