FIR04-00015
| FIR-Aging Inspection | 4/27/2004 | 4/27/2004 | 4/27/2004 12:00:00 AM | | PASS |
|
|
project is still under construction 4/27/2004 10:12:01 AM
|
FIR03-00725
| INSP-Sprinkler Rough-in/Hydro | 4/26/2004 | 4/27/2004 | 4/27/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 4/26/2004 at 1:45:19 PM. Contact: ###-####. R/I and final okay; minor changes to head layout at west end - spacing okay 4/27/2004 1:22:01 PM
|
BLD03-02023
| FIRE-Sprinkler Rough-in | 4/26/2004 | 4/27/2004 | 4/27/2004 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 4/26/2004 at 4:10:31 PM. Contact: ###-####. Need approved plans; tenting problems; water meter is 3/4 inch - plans show 1 inch; head overspaced in game room 4/27/2004 10:11:19 AM
|
BLD04-00438
| FIRE-Final Inspection | 4/26/2004 | 4/27/2004 | 4/27/2004 12:00:00 AM | P | PASS |
|
|
rob; Phone #: ###-#### Internet Inspection Request from: Barbara Moore No card to sign; will have closure on door for structural inspector 4/27/2004 3:57:09 PM
|
FIR04-00248
| INSP-Final Inspection | 4/27/2004 | 4/27/2004 | 4/27/2004 12:00:00 AM | P | PART |
|
|
John; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes The permit as-builts are required as the design area is for obstructed noncombustible and the 3 heads were shown to penetrate the new wall but were installed from the 1.25 inch line in the tenant space; standpipe hose outlet moved to stair well per plans 4/27/2004 2:33:56 PM
|
BLD03-02023
| BLD-Conference | 4/27/2004 | 4/27/2004 | 4/27/2004 12:00:00 AM | P | PART |
|
|
Per Dave Miller the sprinkler flow switch will allowed to activate an outside alarm device instead of connection to the smoke detectors; this info was relayed to Todd of Peak Electric 4/27/2004 3:09:10 PM
|
FIR04-00230
| INSP-Conference | 4/27/2004 | 4/27/2004 | 4/27/2004 12:00:00 AM | P | PART |
|
|
Per Dave Miller the sprinkler flow switch will allowed to activate an outside alarm device instead of connection to the smoke detectors; this info was relayed to Todd of Peak Electric 4/27/2004 3:09:27 PM
|