Inspections for the day of: Tuesday, April 27, 2004.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00015 FIR-Aging Inspection4/27/20044/27/20044/27/2004 12:00:00 AM PASS
project is still under construction 4/27/2004 10:12:01 AM
FIR03-00725 INSP-Sprinkler Rough-in/Hydro4/26/20044/27/20044/27/2004 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 4/26/2004 at 1:45:19 PM. Contact: ###-####. R/I and final okay; minor changes to head layout at west end - spacing okay 4/27/2004 1:22:01 PM
BLD03-02023 FIRE-Sprinkler Rough-in4/26/20044/27/20044/27/2004 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 4/26/2004 at 4:10:31 PM. Contact: ###-####. Need approved plans; tenting problems; water meter is 3/4 inch - plans show 1 inch; head overspaced in game room 4/27/2004 10:11:19 AM
BLD04-00438 FIRE-Final Inspection4/26/20044/27/20044/27/2004 12:00:00 AMPPASS
rob; Phone #: ###-#### Internet Inspection Request from: Barbara Moore No card to sign; will have closure on door for structural inspector 4/27/2004 3:57:09 PM
FIR04-00248 INSP-Final Inspection4/27/20044/27/20044/27/2004 12:00:00 AMPPART
John; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes The permit as-builts are required as the design area is for obstructed noncombustible and the 3 heads were shown to penetrate the new wall but were installed from the 1.25 inch line in the tenant space; standpipe hose outlet moved to stair well per plans 4/27/2004 2:33:56 PM
BLD03-02023 BLD-Conference4/27/20044/27/20044/27/2004 12:00:00 AMPPART
Per Dave Miller the sprinkler flow switch will allowed to activate an outside alarm device instead of connection to the smoke detectors; this info was relayed to Todd of Peak Electric 4/27/2004 3:09:10 PM
FIR04-00230 INSP-Conference4/27/20044/27/20044/27/2004 12:00:00 AMPPART
Per Dave Miller the sprinkler flow switch will allowed to activate an outside alarm device instead of connection to the smoke detectors; this info was relayed to Todd of Peak Electric 4/27/2004 3:09:27 PM