Inspections for the day of: Wednesday, April 27, 2005.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01427 Temporary Service4/26/20054/27/20054/27/2005 8:09:43 AMACANC
Phone #: ###-#### Internet Inspection Request from: Tyler Bowen Inspection cancelled from web by: Tyler Bowen
ELE04-03054 Electrical Rough-In4/26/20054/27/20054/27/2005 12:00:00 AMAPART
2nd FLOOR ROUGH-IN - LATE MORNING IF POSSIBLE. THANKS; Phone #: ###-#### Internet Inspection Request from: Barry Kendall 2nd floor rooms ok 4/27/2005 9:56:05 AM
ELE05-01402 Temporary Service4/26/20054/27/20054/27/2005 12:00:00 AMAPASS
tom; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
t/s u/g new ok 4/27/2005 10:16:27 AM
ELE05-01418 Permanent Service4/25/20054/27/20054/27/2005 12:00:00 AMAPASS
call 1st before insp todd ###-#### -sent to you because its got steve w p/s o/h new ok 4/27/2005 8:01:26 AM
ELE05-01266 Electrical Rough-In4/26/20054/27/20054/27/2005 12:00:00 AMANH
henry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore no access called 4/27/2005 8:34:18 AM
ELE05-01375 Final4/26/20054/27/20054/27/2005 12:00:00 AMPFAIL
We replaced the old 200 amp disconnect, replaced an existing receptacle with a GFCI receptacle, replaced some surface- run smurf tube with conduit.Please call me for access and tour.Thanks!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell cor. grd at p/s shall meet 2005 nec, needs 3/0 from meter to new p/s, high leg orange and B phase, bond hot&cold at both water heaters, bond around metal pipe isolated by plastic pipe with #4 copper isolate grds and neutrals load side of p/s had conference with mitchell elect 4/27/2005 2:16:24 PM
ELE05-00630 Final4/26/20054/27/20054/27/2005 12:00:00 AMPPASS
phil ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok card signed 4/27/2005 3:10:03 PM
ELE05-01434 Electrical Rough-In4/27/20054/27/20054/27/2005 12:00:00 AMPNR
Phone #: ###-#### Internet Inspection Request from: joe wheeler contrac\tor called, he will recshedule 4/27/2005 1:31:22 PM
ELE05-01427 Temporary Service4/27/20054/27/20054/27/2005 12:00:00 AMPFAIL
Phone #: ###-#### Internet Inspection Request from: Tyler Bowen cor. posted called 300.10 needs bond bushings where RE washers are used 4/27/2005 12:05:54 PM
ELE05-01440 Electrical Rough-In4/27/20054/27/20054/27/2005 12:00:00 AMPFAIL
###-#### george cor. posted called 300.4(A)(1)&(D) 11/4" and nail plates everywhere 4/27/2005 12:44:03 PM