ELE05-00903
| Final | 4/27/2005 | 4/27/2005 | 4/27/2005 7:47:25 AM | P | CANC |
|
|
Please do not inspect until 4:00pm, call Dennis with any questions.###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa Inspection cancelled from web by: Daniel Gamboa
|
ELE05-01344
| Electrical Rough-In | 4/26/2005 | 4/27/2005 | 4/27/2005 12:00:00 AM | A | PASS |
|
|
ANY QUESTIONS PLEASE CALL ED SCHALLOCK; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ric walls only ok 4/27/2005 10:17:20 AM
|
ELE05-00816
| Final | 4/26/2005 | 4/27/2005 | 4/27/2005 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 4/26/2005 at 2:34:58 PM. Contact: ###-####. called contr, left message to fix one loose recpt, ok to final 4/27/2005 8:51:32 AM
|
ELE05-00818
| Final | 4/26/2005 | 4/27/2005 | 4/27/2005 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 4/26/2005 at 2:35:51 PM. Contact: ###-####. called contr, left message, left corr notice, 314.21 drywall shall be repaired,406.5 recpt faceplates shall seat against surface, 110.12(C) there shall be no damaged parts(garage gfci) 4/27/2005 8:35:20 AM
|
ELE05-01432
| Electrical Rough-In | 4/26/2005 | 4/27/2005 | 4/27/2005 12:00:00 AM | A | PASS |
|
|
###-#### - dean called contr for nailplate, ric ok 4/27/2005 9:53:21 AM
|
ELE05-01098
| Electrical Rough-In | 4/26/2005 | 4/27/2005 | 4/27/2005 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 4/26/2005 at 6:56:42 PM. Contact: ###-####. corrections made, ric ok 4/27/2005 9:24:27 AM
|
ELE05-01432
| Permanent Service | 4/27/2005 | 4/27/2005 | 4/27/2005 12:00:00 AM | A | PASS |
|
|
p/s u/g n ok
|
ELE05-01445
| Rough-In Permanent Service | 4/27/2005 | 4/27/2005 | 4/27/2005 12:00:00 AM | P | PASS |
|
|
###-#### dan ric ok called contr about 1 1/4", p/s u/g n ok 4/27/2005 3:17:51 PM
|
ELE05-00903
| Electrical Rough-In | 4/27/2005 | 4/27/2005 | 4/27/2005 12:00:00 AM | P | PASS |
|
|
|
ELE05-00903
| Electrical Rough-In | 4/27/2005 | 4/27/2005 | 4/27/2005 12:00:00 AM | P | PASS |
|
|
clg cover ok except where missing light
|
ELE05-01093
| Electrical Rough-In | 4/26/2005 | 4/27/2005 | 4/27/2005 12:00:00 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer called contr, left corr notice, 210.52(A) (2) rcpt shall be added in 2' wall by fireplace, 300.4(D) nm cable shall be 1 1/4" from edge of framing member by pantry, ric ok kitchen dining area 4/27/2005 12:10:10 PM
|
ELE05-00903
| Final | 4/27/2005 | 4/27/2005 | 4/27/2005 12:00:00 AM | P | CANC |
|
|
This is for ceiling final call Dennis with any questions. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa see updated request 4/27/2005 4:26:06 PM
|
ELE05-01430
| Temporary Service | 4/27/2005 | 4/27/2005 | 4/27/2005 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 4/27/2005 at 8:32:21 AM. Contact: ###-####. called contr, left corr notice, fee due, 110.12(C) there shall be no broken parts(50A recpt) BCC Job id shall be posted 4/27/2005 4:17:52 PM
|
ELE05-01430
| Temporary Service | 4/27/2005 | 4/27/2005 | 4/27/2005 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 4/27/2005 at 8:32:21 AM. Contact: ###-####. called contr, left corr notice, fee due, 110.12(C) there shall be no broken parts(50A recpt) BCC Job id shall be posted 4/27/2005 4:17:52 PM
|
ELE04-03568
| Final | 4/27/2005 | 4/27/2005 | 4/27/2005 12:00:00 AM | P | PASS |
|
|
rex; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to final 4/27/2005 2:41:44 PM
|
ELE05-01340
| Electrical Rough-In | 4/27/2005 | 4/27/2005 | 4/27/2005 12:00:00 AM | P | PASS |
|
|
tom; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ric ok 4/27/2005 2:14:53 PM
|
ELE05-01441
| Temporary Service | 4/27/2005 | 4/27/2005 | 4/27/2005 12:00:00 AM | P | FAIL |
|
|
JEREMY ###-#### called contr, left corr notice 250.12 remove paint, 250.8 listed fittings, 590.6 gfci protect 30 and 50a rcpts, 110.12(A) close openings, 300.11 staple gnd cndr, 110.12(C) no broken parts, Bcc job id sticker, re-inspection fee due 4/27/2005 12:43:24 PM
|