Inspections for the day of: Thursday, April 27, 2006.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01414 Electrical Rough-In4/27/20064/27/20064/27/2006 4:41:03 PMPPASS
corr made, ric ok
ELE06-00979 Final4/27/20064/27/20064/27/2006 3:45:48 PMPNH
wrhels ele ; Phone #: ###-#### Internet Inspection Request from: Marsha called contr, he will recall
ELE06-01374 Electrical Rough-In4/27/20064/27/20064/27/2006 2:57:45 PMPPASS
cathy ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie reviewed grounding for piping, no cord for fixed equipment, mc strapping, emt strapping on exposed work ,adding gfci over offices for air heater, ok to cover sheet-rock part in offices, equip has etl labels, ric ok, will do service later
ELE06-01462 Rough-In Permanent Service4/27/20064/27/20064/27/2006 2:39:58 PMPFAIL
john- cell ###-####--call 1st before insp for access called contr, left corr notice, nec 300.4(A) & (D) edge of holes and nm cable shall be 1 1/4" from edge of framing members, 250.86 metal box in garage ceiling shall be grounded, 210.52(A) shall add recpt to wall in lr , BCC all make-up shall be done,smokes and a/c
ELE06-01062 Final4/27/20064/27/20064/27/2006 1:36:05 PMPPASS
Chris; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok to final, signed card for occupancy
ELE06-00925 Electrical Rough-In4/26/20064/27/20064/27/2006 10:32:45 AMACANC
tolly - new addition; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, wrong type permit
ELE06-00925 Permanent Service4/26/20064/27/20064/27/2006 10:26:12 AMACANC
tolly; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, wrong type permit
ELE06-01449 Temporary Service4/26/20064/27/20064/27/2006 9:56:40 AMAPASS
###-#### - mike called contr, left survey, nec 11o.12(C) there shall be no broken parts,50a recpt, 250.24(A) gec shall be connected togrounded conductor term, t/s u/g n ok
ELE06-00865 Final4/26/20064/27/20064/27/2006 9:27:33 AMAPASS
Trent; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung ok to final, signed struct card
ELE06-00115 Final4/26/20064/27/20064/27/2006 8:53:43 AMAPASS
code=2241; Phone #: ###-#### Internet Inspection Request from: William Zerfas called contr to put cover on gec access point, irrigation pump later under new permit. ok to final
ELE06-00416 Permanent Service4/26/20064/27/20064/27/2006 5:34:36 AMPPASS
Phone #: ###-#### Internet Inspection Request from: todd hall p/s u/g rec ok, told elect and contractor about nec 230.7, no feeder wire in service wireway