Inspections for the day of: Friday, April 27, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00800 INSP-Sprinkler Rough-in4/26/20074/27/20075/1/2007 4:14:40 PMPPART
OH rough-in for the penthouse, 6th and 5th floors are approved, noted one overspaced head at the penthouse to be relocated, also checked previous noted defficiencies on the other floors.
FIR06-00780 FIR-Aging Inspection4/27/20074/27/20075/1/2007 12:30:59 PM DEFR
FIR06-00595 INSP-Alarm Testing4/27/20074/27/20074/27/2007 5:46:22 PMPPART
See comments per field inspection by M. Timmerman scheduled for 4/28.
FIR06-00992 INSP-Final Inspection4/27/20074/27/20074/27/2007 5:44:30 PMPPASS
Fire sprinkler permit finaled.
FIR06-00495 INSP-Final Inspection4/26/20074/27/20074/27/2007 3:24:33 PMAPART
Tested previously noted correction items at unit 210 and 312. Open horn circut #3 on the panel at time of inspection due to contractor in process of repair for temporal pattern at the 5th floor notification devices, final pending completion of this issue and satisfactory test of the remaining alarm work.
FIR07-00335 INSP-Final Inspection4/26/20074/27/20074/27/2007 2:12:56 PMPPASS
Fire alarm reinspection passed, permit finaled.
FIR07-00364 INSP-Sprinkler Rough-in4/27/20074/27/20074/27/2007 2:11:44 PMPPART
UG fire supply line and remote FDC piping are approved for cover.
FIR06-00504 INSP-Sprinkler Rough-in4/25/20074/27/20074/27/2007 11:46:14 AMPFAIL
Inspection for the terrace portions of the 3rd and 4th floor failed due to overspaced heads, missing heads and lines which need to be reconfigured as discussed.
FIR06-00540 INSP-Sprinkler Rough-in/Hydro4/26/20074/27/20074/27/2007 11:42:30 AMAPART
OH rough-in inspection for the 1st floor SE quad as marked on plans is approved for cover, hydrostatic testing for this portion of the system also completed satisfactory.
BLD07-00413 FIRE-Final Inspection4/26/20074/27/20074/27/2007 11:40:21 AMAPASS
Fire life safety inspection passed.
FIR07-00239 INSP-Final Inspection4/27/20074/27/20074/27/2007 11:39:39 AMPPASS
Fire sprinkler permit finaled.