BLD06-02189
| FIRE-Final Inspection | 4/27/2007 | 4/27/2007 | 4/27/2007 4:54:17 PM | P | CANC |
|
|
I ran out of time to perform inspection today. Will need to reschedule.
|
BLD06-02841
| FIRE-Final Inspection | 4/26/2007 | 4/27/2007 | 4/27/2007 4:50:35 PM | P | FAIL |
|
|
Exit lights and emergency lights do not work.
|
BLD06-00454
| FIRE-Final Inspection | 4/26/2007 | 4/27/2007 | 4/27/2007 4:49:35 PM | A | FAIL |
|
|
Life safety will be ok to final when the alarm permits are finaled.
|
BLD06-00453
| FIRE-Final Inspection | 4/26/2007 | 4/27/2007 | 4/27/2007 4:48:56 PM | A | FAIL |
|
|
Life safety will be ok to final when the alarm permits are finaled.
|
FIR06-00918
| INSP-Final Inspection | 4/27/2007 | 4/27/2007 | 4/27/2007 4:47:43 PM | P | FAIL |
|
|
Per Brian the fire alarm system strobes do not sync and the remote indicators for the duct smoke detectors are wrong
|
BLD06-03621
| FIRE-Final Inspection | 4/27/2007 | 4/27/2007 | 4/27/2007 4:28:56 PM | P | PASS |
|
|
life safety passed.
|
FIR06-00941
| INSP-Final Inspection | 4/27/2007 | 4/27/2007 | 4/27/2007 4:27:03 PM | P | PASS |
|
|
permit finaled
|
FIR05-00536
| INSP-Sprinkler Rough-in/Hydro | 4/26/2007 | 4/27/2007 | 4/27/2007 3:56:10 PM | A | PASS |
|
|
See the city approved plans for the location at the main entrance where the sprinkler piping is ok to cover.
|
FIR06-00941
| INSP-Final Inspection | 4/27/2007 | 4/27/2007 | 4/27/2007 2:22:50 PM | P | FAIL |
|
|
Per Brian the tamper switchs need adjusting so that a correct signal is given at the fire alarm panel
|
FIR06-00591
| INSP-Final Inspection | 4/27/2007 | 4/27/2007 | 4/27/2007 2:21:01 PM | P | PASS |
|
|
permit finaled
|
FIR07-00278
| INSP-Sprinkler Rough-in | 4/26/2007 | 4/27/2007 | 4/27/2007 2:14:07 PM | A | FAIL |
|
|
Pendant heads exceed the original design of 120sq/ft. Infact they exceed 130 sq/ft allowed for ordinary hazard. The existing upright heads are spaced at 165 sq/ft along the west wall and the piping to the pendants is hung from the bottom cord of the trusses. Uprights will need to be added and the hangers moved to the top of the truss or provide documentation that they can be hung from the bottom as discussed.
|
MIS06-00281
| FIR-Final | 4/26/2007 | 4/27/2007 | 4/27/2007 1:35:17 PM | A | PASS |
|
|
Life safety passed and card is now signed.
|
FIR07-00370
| INSP-Final Inspection | 4/27/2007 | 4/27/2007 | 4/27/2007 1:25:58 PM | P | PASS |
|
|
permit finaled per Brian
|
FIR06-00536
| INSP-Sprinkler Rough-in/Hydro | 4/26/2007 | 4/27/2007 | 4/27/2007 1:09:37 PM | A | PASS |
|
|
Hydro test of the overhead piping is passed. Fire pump and fdc stills needs hydro testing
|
FIR07-00171
| INSP-Final Inspection | 4/26/2007 | 4/27/2007 | 4/27/2007 11:22:16 AM | A | PASS |
|
|
permit finaled
|
BLD06-02189
| FIRE-Final Inspection | 4/26/2007 | 4/27/2007 | 4/27/2007 10:49:26 AM | A | FAIL |
|
|
Need air balance reports, need panels on both ends of the long john silvers hood, remote annunciators for the duct detectors are wrong, exit signs dont work, exit discharge lighting is not installed, no address.........ect
|
FIR07-00369
| INSP-Final Inspection | 4/26/2007 | 4/27/2007 | 4/27/2007 10:47:13 AM | A | PASS |
|
|
hood suppression system operated correctly
|
FIR07-00260
| INSP-Final Inspection | 4/27/2007 | 4/27/2007 | 4/27/2007 10:10:48 AM | P | PASS |
|
|
permit finaled
|
BLD06-00931
| FIRE-Final Inspection | 4/26/2007 | 4/27/2007 | 4/27/2007 10:06:09 AM | A | FAIL |
|
|
Need fire extinguishers, apartment addresses and building address. Smoke detectors have been tested.
|
FIR06-00941
| INSP-Sprinkler Rough-in/Hydro | 4/27/2007 | 4/27/2007 | 4/27/2007 9:08:10 AM | P | CANC |
|
|
Jonathan is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
|
FIR06-00724
| INSP-Sprinkler Rough-in | 4/27/2007 | 4/27/2007 | 4/27/2007 12:00:00 AM | P | CANC |
|
|
terry; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|