BLD06-02303
| FIRE-Final Inspection | 4/27/2009 | 4/27/2009 | 4/27/2009 5:17:28 PM | P | PART |
|
|
Work in progress at dry sprinkler risers for the 3rd and 4th floors, phone line at the command center to be installed 4/28 per contractor, discussed remainder of items needed for fire life safety and generator test for egress lighting.
|
BLD08-00712
| FIRE-Final Inspection | 4/24/2009 | 4/27/2009 | 4/27/2009 5:13:12 PM | P | PASS |
|
|
Fire life safety inspection passed. NOTE: Elevator recall functions are car and hoistway specific- fire alarm system initiating and notification has not been required, therefore no fire alarm permit work is project attatched, notification devices at the elevator lobbys have been removed to meet these parameters.
|
FIR07-00971
| INSP-Alarm Testing | 4/23/2009 | 4/27/2009 | 4/27/2009 3:51:35 PM | P | NR |
|
|
Scheduled by a contractor via Hello! on 4/23/2009 at 10:21:08 AM. Contact: ###-####. Contractor not available for site inspection per phone conversation.
|
FIR09-00127
| INSP-Sprinkler Rough-in/Hydro | 4/27/2009 | 4/27/2009 | 4/27/2009 3:23:01 PM | P | PART |
|
|
Begin air testing at 3:00 pm @ 41.5 psig.
|
BLD08-02286
| FIRE-Final Inspection | 4/24/2009 | 4/27/2009 | 4/27/2009 2:44:15 PM | P | FAIL |
|
|
See fire code review notes for stipulations regarding fire alarm permit work due to relocated magnetic door hold opens at fire doors, remainder of project fire life safety appears satisfactory.
|
FIR08-00832
| INSP-Sprinkler Rough-in/Hydro | 4/24/2009 | 4/27/2009 | 4/27/2009 2:18:20 PM | P | CANC |
|
|
Overbooked
|
BLD07-01845
| FIRE-Final Inspection | 4/27/2009 | 4/27/2009 | 4/27/2009 2:17:11 PM | P | CANC |
|
|
Overbooked
|
FIR08-00787
| INSP-Final Inspection | 4/23/2009 | 4/27/2009 | 4/27/2009 2:14:45 PM | P | CANC |
|
|
Overbooked
|
FIR08-00094
| INSP-Sprinkler Rough-in/Hydro | 4/27/2009 | 4/27/2009 | 4/27/2009 2:14:15 PM | P | CANC |
|
|
Overbooked
|
FIR09-00127
| INSP-Sprinkler Rough-in/Hydro | 4/27/2009 | 4/27/2009 | 4/27/2009 1:27:06 PM | A | PART |
|
|
OH hydrostatic retest of the preaction system passed.
|
BLD09-00380
| FIRE-Final Inspection | 4/24/2009 | 4/27/2009 | 4/27/2009 1:26:02 PM | A | PASS |
|
|
Items on the issued correction notice field verified for completion, manual thumbturn locksets have been disabled in lieu of removal. Life safety finaled.
|
BLD08-02166
| FIRE-Final Inspection | 4/24/2009 | 4/27/2009 | 4/27/2009 12:15:07 PM | A | FAIL |
|
|
Door hardware at the mail room and conference room B-316 need repair, missing max occupant load sign at the sawtooth conference room, post directional signage per red lines on approved plan set, door closure may be needed at the second exit door from room B-316.
|
FIR09-00015
| FIR-Aging Inspection | 4/27/2009 | 4/27/2009 | 4/27/2009 11:32:55 AM | | DONE |
|
|
Need site inspection request for work completed.
|
FIR09-00240
| INSP-Final Inspection | 4/24/2009 | 4/27/2009 | 4/27/2009 11:30:13 AM | A | CANC |
|
|
Overbooked
|
BLD09-00438
| FIRE-Final Inspection | 4/23/2009 | 4/27/2009 | 4/27/2009 11:28:50 AM | A | CANC |
|
|
Overbooked
|