ELE10-00897
| Temporary Service | 4/27/2010 | 4/27/2010 | 4/28/2010 6:13:43 AM | P | CANC |
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### see 4/28/10 request
|
ELE10-00896
| Temporary Service | 4/27/2010 | 4/27/2010 | 4/28/2010 6:12:51 AM | P | CANC |
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### see 4/28/10 request
|
ELE10-00125
| Final | 4/26/2010 | 4/27/2010 | 4/27/2010 3:52:11 PM | P | PART |
|
|
Inspection requested from web by: Justin Frates corrections not made, had owner call 414 to confirm need for convenience outlet, tub opening not ready, will need to call for final when done
|
ELE10-00477
| Electrical Rough-In | 4/26/2010 | 4/27/2010 | 4/27/2010 3:26:15 PM | P | PASS |
|
|
Rough in 2 added offices. Call Doug to get in at ###-#### Inspection requested from web by: Barbara Szurgot Phone #: ###-#### walls only ok for 2 new offices, no esc this project
|
ELE10-00888
| Electrical Rough-In | 4/27/2010 | 4/27/2010 | 4/27/2010 2:27:38 PM | P | FAIL |
|
|
Inspection requested from web by: Brandon Blackham Phone #: ###-#### called , left correction notice, NEC 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 334.23 shall protect cables within 6' of attic access, NOTE corrections shall be made within 5 working days
|
ELE10-00883
| Electrical Rough-In | 4/26/2010 | 4/27/2010 | 4/27/2010 1:24:33 PM | P | PASS |
|
|
Pool Bonding--Underground cover Inspection requested from web by: Kevin Koomler Phone #: ###-#### pool bonding ok, u/g ok to cover
|
ELE09-00393
| Final | 4/27/2010 | 4/27/2010 | 4/27/2010 12:56:23 PM | P | PASS |
|
|
michael - please call 1/2 hr prior Phone #: ###-#### called, ok to final, no esc
|
ELE10-00797
| Rough-In Permanent Service | 4/26/2010 | 4/27/2010 | 4/27/2010 12:25:19 PM | P | CANC |
|
|
Any questions please call, thx! Terry W. Inspection requested from web by: Stephen Kren Phone #: ###-#### see conf
|
ELE10-00797
| Conference | 4/27/2010 | 4/27/2010 | 4/27/2010 12:25:09 PM | P | DONE |
|
|
Any questions please call, thx! Terry W. Inspection requested from web by: Stephen Kren Phone #: ###-#### called, told to group permits, existing service doesn't seem to have ground, open knock-outs, new work has no nailplates in 2x4 on edge, told to re-visit job and call back in
|
ELE09-02163
| Final | 4/26/2010 | 4/27/2010 | 4/27/2010 11:34:18 AM | A | PASS |
|
|
Inspection requested from web by: Kevin Koomler Phone #: ###-#### ok to final
|
ELE10-00868
| Electrical Rough-In | 4/26/2010 | 4/27/2010 | 4/27/2010 10:09:57 AM | A | PASS |
|
|
dino Phone #: ###-#### corrections made, ric ok
|
ELE09-02337
| Electrical Rough-In | 4/26/2010 | 4/27/2010 | 4/27/2010 9:39:08 AM | A | PASS |
|
|
Underground Inspection requested from web by: Clint Tate Phone #: ###-#### u/g to dispensers ok
|
ELE10-00651
| Final | 4/26/2010 | 4/27/2010 | 4/27/2010 9:01:01 AM | A | PASS |
|
|
Ron Phone #: ###-#### ok to final
|
ELE10-00861
| Permanent Service | 4/26/2010 | 4/27/2010 | 4/27/2010 8:26:32 AM | A | PASS |
|
|
Inspection requested from web by: John VanZandt Phone #: ###-#### corrections made, p/s o/h rec ok, no esc this project
|