Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-01002 BLD-Aging Inspection4/27/20104/27/20105/4/2010 7:31:15 AMPDONE
BLD06-00962 BLD-Aging Inspection4/27/20104/27/20105/4/2010 7:30:58 AMPDONE
FIR10-00136 INSP-Conference4/27/20104/27/20104/28/2010 5:08:36 PMPDONE
Regarding fire alarm system requirements for R1 occupancies per IFC.
BLD09-01727 FIRE-Final Inspection4/26/20104/27/20104/27/2010 5:35:32 PMAPASS
Fire life safety final inspection passed.
FIR07-00197 INSP-Final Inspection4/21/20104/27/20104/27/2010 5:34:17 PMPPASS
Scope of fire sprinkler work field verified for completion, stamped plans reviewed, inspection passed- permit finaled.
FIR06-00754 INSP-Final Inspection4/21/20104/27/20104/27/2010 5:33:55 PMPPASS
Scope of fire sprinkler work field verified for completion, stamped plans reviewed, inspection passed- permit finaled.
FIR06-00102 INSP-Final Inspection4/21/20104/27/20104/27/2010 5:33:21 PMPPASS
Scope of fire sprinkler work field verified for completion, stamped plans reviewed, inspection passed- permit finaled.
FIR07-00019 INSP-Final Inspection4/21/20104/27/20104/27/2010 5:32:57 PMPPASS
Scope of fire sprinkler work field verified for completion, stamped plans reviewed, inspection passed- permit finaled.
BLD10-00115 FIRE-Final Inspection4/27/20104/27/20104/27/2010 5:28:14 PMPPASS
C/N items finished, fire life safety finaled.
BLD10-00733 FIRE-Final Inspection4/27/20104/27/20104/27/2010 5:27:01 PMPPASS
Noted corrections field verified for compliance, life safety passed.
FIR09-00709 INSP-Final Inspection4/26/20104/27/20104/27/2010 12:56:50 PMAPASS
Scope of fire sprinkler work passed final walkthrough, noted corrections finished, inspection passed.
FIR09-00540 INSP-Final Inspection4/26/20104/27/20104/27/2010 12:54:57 PMADEFR
Pending project related fire alarm permit FIR10-00057- no field inspection request by contractor on this permit to date. Fire alarm work must pass functional testing and final approval in sequence with sprinkler final.
BLD10-00787 FIRE-Final Inspection4/26/20104/27/20104/27/2010 12:48:04 PMAFAIL
Fire extinguishers are three years overdue certification, no access to the adjacent tenant space or riser room to complete inspection, need to provide verification of a current annual inspection for the existing fire sprinkler system.
FIR10-00129 INSP-Final Inspection4/26/20104/27/20104/27/2010 12:43:59 PMAPART
Scope of work completed with the exception of one pendent head at exam room 210 to be re-cut.
BLD10-00539 FIRE-Final Inspection4/23/20104/27/20104/27/2010 12:00:00 AMAFAIL
Life Safety Inspection failed. Tenant space needs to correct the following items:
1) Provide approved door hardware - see inspector comments on plans for details.
2) Remove the keyed locking door hardware at the West exit (Ref. IFC 1008.1.8.3).
3) Cover open receptacles and open light switch outlets in the kitchen area.
4) Install minimum 2A:10:B:C rated fire extinguisher at an accessible location for occupant use. Extinguisher shall have a current inspection tag affixed.
5) Install sign at main entrance "This Door To Remain Unlocked When Building Is Occupied."
BLD10-00291 FIRE-Final Inspection4/26/20104/27/20104/27/2010 12:00:00 AMAPASS
Fire and life safety inspection PASS. Contractor could not locate inspection card, athough the Fire/Life safety inspection is satisfactory.