BLD06-01002
| BLD-Aging Inspection | 4/27/2010 | 4/27/2010 | 5/4/2010 7:31:15 AM | P | DONE |
|
|
|
BLD06-00962
| BLD-Aging Inspection | 4/27/2010 | 4/27/2010 | 5/4/2010 7:30:58 AM | P | DONE |
|
|
|
FIR10-00136
| INSP-Conference | 4/27/2010 | 4/27/2010 | 4/28/2010 5:08:36 PM | P | DONE |
|
|
Regarding fire alarm system requirements for R1 occupancies per IFC.
|
BLD09-01727
| FIRE-Final Inspection | 4/26/2010 | 4/27/2010 | 4/27/2010 5:35:32 PM | A | PASS |
|
|
Fire life safety final inspection passed.
|
FIR07-00197
| INSP-Final Inspection | 4/21/2010 | 4/27/2010 | 4/27/2010 5:34:17 PM | P | PASS |
|
|
Scope of fire sprinkler work field verified for completion, stamped plans reviewed, inspection passed- permit finaled.
|
FIR06-00754
| INSP-Final Inspection | 4/21/2010 | 4/27/2010 | 4/27/2010 5:33:55 PM | P | PASS |
|
|
Scope of fire sprinkler work field verified for completion, stamped plans reviewed, inspection passed- permit finaled.
|
FIR06-00102
| INSP-Final Inspection | 4/21/2010 | 4/27/2010 | 4/27/2010 5:33:21 PM | P | PASS |
|
|
Scope of fire sprinkler work field verified for completion, stamped plans reviewed, inspection passed- permit finaled.
|
FIR07-00019
| INSP-Final Inspection | 4/21/2010 | 4/27/2010 | 4/27/2010 5:32:57 PM | P | PASS |
|
|
Scope of fire sprinkler work field verified for completion, stamped plans reviewed, inspection passed- permit finaled.
|
BLD10-00115
| FIRE-Final Inspection | 4/27/2010 | 4/27/2010 | 4/27/2010 5:28:14 PM | P | PASS |
|
|
C/N items finished, fire life safety finaled.
|
BLD10-00733
| FIRE-Final Inspection | 4/27/2010 | 4/27/2010 | 4/27/2010 5:27:01 PM | P | PASS |
|
|
Noted corrections field verified for compliance, life safety passed.
|
FIR09-00709
| INSP-Final Inspection | 4/26/2010 | 4/27/2010 | 4/27/2010 12:56:50 PM | A | PASS |
|
|
Scope of fire sprinkler work passed final walkthrough, noted corrections finished, inspection passed.
|
FIR09-00540
| INSP-Final Inspection | 4/26/2010 | 4/27/2010 | 4/27/2010 12:54:57 PM | A | DEFR |
|
|
Pending project related fire alarm permit FIR10-00057- no field inspection request by contractor on this permit to date. Fire alarm work must pass functional testing and final approval in sequence with sprinkler final.
|
BLD10-00787
| FIRE-Final Inspection | 4/26/2010 | 4/27/2010 | 4/27/2010 12:48:04 PM | A | FAIL |
|
|
Fire extinguishers are three years overdue certification, no access to the adjacent tenant space or riser room to complete inspection, need to provide verification of a current annual inspection for the existing fire sprinkler system.
|
FIR10-00129
| INSP-Final Inspection | 4/26/2010 | 4/27/2010 | 4/27/2010 12:43:59 PM | A | PART |
|
|
Scope of work completed with the exception of one pendent head at exam room 210 to be re-cut.
|
BLD10-00539
| FIRE-Final Inspection | 4/23/2010 | 4/27/2010 | 4/27/2010 12:00:00 AM | A | FAIL |
|
|
Life Safety Inspection failed. Tenant space needs to correct the following items:
1) Provide approved door hardware - see inspector comments on plans for details.
2) Remove the keyed locking door hardware at the West exit (Ref. IFC 1008.1.8.3).
3) Cover open receptacles and open light switch outlets in the kitchen area.
4) Install minimum 2A:10:B:C rated fire extinguisher at an accessible location for occupant use. Extinguisher shall have a current inspection tag affixed.
5) Install sign at main entrance "This Door To Remain Unlocked When Building Is Occupied."
|
BLD10-00291
| FIRE-Final Inspection | 4/26/2010 | 4/27/2010 | 4/27/2010 12:00:00 AM | A | PASS |
|
|
Fire and life safety inspection PASS. Contractor could not locate inspection card, athough the Fire/Life safety inspection is satisfactory.
|