Inspections for the day of: Friday, April 27, 2012.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00161 INSP-Sprinkler Rough-in/Hydro4/27/20124/27/20124/27/2012 3:57:47 PMPFAIL
The hydro test for the standpipe failed due to a visible pressure loss on four of five pressure guages.
BLD11-01267 FIRE-Conference4/27/20124/27/20124/27/2012 3:53:59 PMPDONE
The standpipe hose valves located on all of the floors at the fire wall per the sprinkler plans were to be mounted recessed in the corridor walls. They have been installed surface mounted on the walls and are possibly encroaching into the egress path. After speaking to Dan Stuart, I spoke to the job site superintendant about having the architect submit to the plan reviewer for approval of this installation.
BLD11-01268 FIRE-Conference4/27/20124/27/20124/27/2012 3:53:15 PMPDONE
The standpipe hose valves located on all of the floors at the fire wall per the sprinkler plans were to be mounted recessed in the corridor walls. They have been installed surface mounted on the walls and are possibly encroaching into the egress path. After speaking to Dan Stuart, I spoke to the job site superintendant about having the architect submit to the plan reviewer for approval of this installation.
BLD11-01269 FIRE-Conference4/27/20124/27/20124/27/2012 3:52:05 PMPDONE
The standpipe hose valves located on all of the floors at the fire wall per the sprinkler plans were to be mounted recessed in the corridor walls. They have been installed surface mounted on the walls and are possibly encroaching into the egress path. After speaking to Dan Stuart, I spoke to the job site superintendant about having the architect submit to the plan reviewer for approval of this installation.
FIR12-00178 INSP-Sprinkler Rough-in4/27/20124/27/20124/27/2012 3:43:38 PMPPASS
Hard lids ok to cover.
FIR12-00202 INSP-Sprinkler Rough-in4/27/20124/27/20124/27/2012 3:43:07 PMPPASS
Hard lids ok to cover.
BLD12-00243 FIRE-Final Inspection4/27/20124/27/20124/27/2012 2:55:49 PMPPASS
life safety passed
FIR12-00173 INSP-Final Inspection4/27/20124/27/20124/27/2012 2:39:51 PMPPASS
permit finaled
FIR12-00183 INSP-Final Inspection4/26/20124/27/20124/27/2012 9:20:46 AMAPASS
Permit finaled