FIR15-00649
| INSP-Final Inspection | 4/26/2016 | 4/27/2016 | 4/28/2016 10:52:27 AM | A | CANC |
|
|
Nathan with TVFP is following up on whether additional coverage is needed under the new balcony.
|
FIR16-00052
| INSP-Supply line flush | 4/27/2016 | 4/27/2016 | 4/27/2016 2:39:50 PM | P | PART |
|
|
The underground supply piping is ok to cover up to the first thrust block. Thrust blocks are being mixed by hand and were not done at the time of inspection. I noted that the piping from the 90 to the base of the riser is not at 4'-6" and will need to be buried deeper or landscaping performed to reach the required bury dept.
I also did a basic rough-in inspection on the overhead piping. For the most part everything is complete except for the riser build, eartquake bracing and draft stops required by the upright sprinkler heads. Plans need to be provided to plan review showing the additional fittings and elevation changes as well as the change of piping/heads in the rooms on the west side of the building where sidewalls are now being used. The said sidewalls are installed 3 1/2" below the ceiling so I will need verification they are listed for this.
|
BLD16-00442
| FIRE-Final Inspection | 4/27/2016 | 4/27/2016 | 4/27/2016 2:23:49 PM | P | CANC |
|
|
would like call ahead; Josh Phone #: ###-####
|
FIR16-00216
| INSP-Final Inspection | 4/27/2016 | 4/27/2016 | 4/27/2016 2:22:54 PM | P | FAIL |
|
|
No actual testing performed due to the a/v's being mounted too low.
|
FIR15-00828
| INSP-Sprinkler Rough-in/Hydro | 4/26/2016 | 4/27/2016 | 4/27/2016 11:04:31 AM | A | PASS |
|
|
Underground hydro passed
|
BLD14-02705
| FIRE-Final Inspection | 4/26/2016 | 4/27/2016 | 4/27/2016 9:18:45 AM | A | FAIL |
|
|
Resubmit plans showing all wall changes and include the new occupancy classifications. (Include the enlarged Accounting area and the large A3 area). Route these updated plans for a Fire Life Safety review. It appears that the existing fire alarm system will require modifications for the A3 and B occupancies. Provide verification that additional sprinkler coverage is not required under the new balcony.
|
BLD16-00442
| FIRE-Final Inspection | 4/26/2016 | 4/27/2016 | 4/27/2016 7:59:40 AM | A | FAIL |
|
|
Need all of the city approved plans and small documents. Need current inspection for the fire extinguishers.
|
FIR16-00209
| INSP-Sprinkler Rough-in | 4/26/2016 | 4/27/2016 | 4/27/2016 7:33:04 AM | A | PASS |
|
|
Piping is ok to cover
|