Inspections for the day of: Wednesday, April 27, 2016.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-00956 FIRE-Final Inspection4/26/20164/27/20164/27/2016 2:49:29 PMPPASS
No fire sprinklers, no fire alarms, fire extinguisher is in tenant space, tenant will hang fire extinguisher in discussed locatio when painting is finished. Final life fire safety inspection passed/complete.
FIR16-00234 INSP-Sprinkler Rough-in4/27/20164/27/20164/27/2016 11:09:59 AMPPASS
Previously noted items above restroom hardlids addressed, pendeant head in mens room relocated for proper spacing, upright head added to cover exposed combustible material that is attached to restroom ceiling joist. Overhead fire sprinkler piping above restroom hardlids approved for cover.
FIR16-00102 INSP-Sprinkler Rough-in/Hydro4/26/20164/27/20164/27/2016 9:28:08 AMPPASS
Overhead rough to cover inspection complete for ceiling grid area's, all overhead fire sprinkler piping on level 3 approved for cover. 200 psi hydrostatic test passed/complete for level 3.
FIR16-00280 INSP-Sprinkler Rough-in4/26/20164/27/20164/27/2016 8:29:12 AMAPASS
Rough to cover inspection complete for sprinkler modifications in elevator lobby, basement level, overhead fire sprinkler piping in elevator lobby approved for cover.