Inspections for the day of: Thursday, April 27, 2017.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00738 INSP-Sprinkler Rough-in/Hydro4/26/20174/27/20174/27/2017 3:30:31 PMAFAIL
24 hour air test failed.
FIR17-00002 INSP-Sprinkler Rough-in4/26/20174/27/20174/27/2017 3:29:48 PMPPART
Plans need to be resubmitted for plan modifications that include the actual pipe routing and fitting counts, branchline restraints are missing on the two most south west branchlines, branch line restraints are required on the grid branchlines (41'max), FDC is not approved at its current location, heads are spaced too far off of a wall at the west end of the building, piping over Conference room can be recovered, the nuts on the side sammys can be unthreaded by finger so they need to be tightened down.
FIR17-00122 INSP-Sprinkler Rough-in4/27/20174/27/20174/27/2017 3:19:29 PMPPASS
Rough-in passed. I questioned some pipe connections that will need to be verified prior to a final
BLD16-02699 FIRE-Final Inspection4/27/20174/27/20174/27/2017 1:51:55 PMPFAIL
repair the two exit discharge lights at the main exit
BLD15-00048 FIRE-Final Inspection4/26/20174/27/20174/27/2017 1:48:52 PMPPASS
life safety passed
BLD16-03038 FIRE-Final Inspection4/27/20174/27/20174/27/2017 11:15:38 AMPPASS
life safety passed
BLD17-00973 FIRE-Final Inspection4/27/20174/27/20174/27/2017 10:38:10 AMPPASS
life safety passed
FIR16-00454 INSP-Final Inspection4/26/20174/27/20174/27/2017 10:37:02 AMPFAIL
Horns do not sync as required
BLD16-01092 FIRE-Final Inspection4/26/20174/27/20174/27/2017 10:32:11 AMACANC
still waiting for the fire alarm permit to be addressed
FIR16-00588 INSP-Final Inspection4/26/20174/27/20174/27/2017 10:31:36 AMAPASS
permit finaled
FIR17-00172 INSP-Final Inspection4/26/20174/27/20174/26/2017 12:12:19 PMAPASS
permit finaled