Inspections for the day of: Monday, April 27, 2020.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-02894 Electrical Rough-In4/27/20204/27/20204/27/2020 3:47:59 PMPDONE
ok with video/photo // larry Phone #: ###-####...occupied home with homeowner doing work...discussed with him COVID19 inspection protocals...non essential work...inspection will be done by pics sent thru email...waiting on email..follow up inspection scheduled for next day
ELE20-01368 Final4/24/20204/27/20204/27/2020 3:23:57 PMPPASS
crew will be ready in afternoon after 1pm for final ###-#### Phone #: ###-#### Inspection requested via web by Terissa Morain...
labelling, disconnect, and OCPD ok
ELE20-01186 Permanent Service4/27/20204/27/20204/27/2020 2:55:09 PMPPASS
Phone #: ###-#### Inspection requested via web by jamie berg....
correction made
uffer connection shall be accessible at final
p/s u/g new ok...back of property
ELE19-03961 Electrical Rough-In4/26/20204/27/20204/27/2020 1:49:45 PMPPASS
3rd floor units Phone #: ###-#### Inspection requested via web by Todd Hall...
3rd floor units and breezeway up to heat tape junction box ok to cover
ELE19-04581 Final4/27/20204/27/20204/27/2020 1:11:42 PMPPART
Phone #: ###-#### Inspection requested via web by Brad Girard...
temp occupency given...remaining
labelling of panels and HVAC units, misc thru out building, service ground protection, and all equipment for UL verification,circuitry, breaker size
ELE20-01398 Electrical Rough-In4/24/20204/27/20204/27/2020 12:25:21 PMPFAIL
ready for electrical ground work inspection crew will be back onsite in the afternoon Phone #: ###-#### Inspection requested via web by Terissa Morain...
1) trench shall be a minimum 18" deep to top of pipe...2 open ends not deep enough...require mid point opened up to verify depth
ELE20-01400 Electrical Rough-In4/23/20204/27/20204/27/2020 11:42:11 AMAFAIL
Please call Roger for access information prior to arrival.
Secured area of access. Phone #: ###-#### Inspection requested via web by Kevin Perez...no access...called contact number multiple times...no answer
ELE20-01447 Temporary Service4/27/20204/27/20204/27/2020 11:30:36 AMPPASS
Phone #: ###-#### Inspection requested via web by Dan Rohl...t/s u/g new ok
ELE20-00918 Final4/27/20204/27/20204/27/2020 11:14:51 AMPPASS
Mike Phone #: ###-####...ok to final
ELE20-01064 Final4/27/20204/27/20204/27/2020 10:26:34 AMPPASS
Phone #: ###-#### Inspection requested via web by Greg Idsinga...job complete..ok to final
ELE20-01088 Electrical Rough-In4/27/20204/27/20204/27/2020 10:00:21 AMAPASS
Phone #: ###-#### Inspection requested via web by Scott Campbell...interior ceiling drops for cans x 3 areas...cans will be cut in after sheetrock installed
ELE19-04181 Electrical Rough-In4/26/20204/27/20204/27/2020 9:39:13 AMAPASS
Give me a call when you arrive. I will be on site
thanks,
Ron Phone #: ###-#### Inspection requested via web by Ron Zimmerman...
new ceiling grid...several areas ok to cover...areas given on tag...E hallway, men's bath, breakroom, electrical rm office, locker room, front entry...
ELE19-04181 Electrical Rough-In4/27/20204/27/20204/27/2020 9:37:18 AMAFAIL
Give me a call when you arrive. I will be on site
thanks,
Ron Phone #: ###-#### Inspection requested via web by Ron Zimmerman...

correction notice given
1) all data cabling, fire alarm wiring, and any low voltage wiring will be support and not laying on grid
2) S/O cord being used as permanent wiring shall be removed...S/O not rated for permanent wiring or used above grid
ELE20-01424 Rough-In Permanent Service4/25/20204/27/20204/27/2020 8:56:45 AMAPASS
Phone #: ###-#### Inspection requested via web by Troy Ballard...
rough ok to cover
p/s u/g new ok
MIS20-00131 ELE-Conference4/24/20204/27/20204/27/2020 8:14:12 AMAPASS
correction notice given to park manager
5 days given to start proceedings to pull permit and get inspections...park ordiinance is no tampering to park pedistal allowed
ELE19-03639 Electrical Rough-In4/26/20204/27/20204/27/2020 7:03:09 AMPCANC
first floor ceiling drops Phone #: ###-#### >> Inspection requested via web by Todd Hall Inspection cancelled from web by: Todd Hall