Inspections for the day of: Monday, April 27, 2020.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-00493 Electrical Rough-In4/27/20204/27/20204/27/2020 2:36:43 PMPPASS
Contact: Wes Powell, wall rough-in inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden
1/2 wall stubs in hager bay ok to cover
ELE20-01100 Permanent Service4/27/20204/27/20204/27/2020 1:43:44 PMPPASS
Contact: Jeremy Thornock Phone #: ###-#### Inspection requested via web by Deb Gooden
p/s u/g n ok 1 meter
ELE20-01428 Permanent Service4/27/20204/27/20204/27/2020 1:43:12 PMPPASS
Contact: Jeremy Thornock Phone #: ###-#### Inspection requested via web by Deb Gooden
2 units 120@122
p/s u/g n ok 2 meters needed
ELE20-01435 Electrical Rough-In4/24/20204/27/20204/27/2020 1:14:34 PMPPASS
Concrete encased electrode. Contact with any questions Phone #: ###-#### Inspection requested via web by Kory Peterson
Uffer ok to cover
MIS20-00132 ELE-Conference4/24/20204/27/20204/27/2020 11:24:04 AMADONE
Need p@z and building permits in order to ove forward
ELE20-01407 Conference4/25/20204/27/20204/27/2020 11:23:22 AMADONE
Phone #: ###-#### Inspection requested via web by Keith Chetta
Discussed wiring size as per 550 and meeting min 100 amp feeder conductor sizing and may change terminations to 75 degree column for conduit sizing
ELE20-00915 Final4/24/20204/27/20204/27/2020 10:34:12 AMAPASS
Phone #: ###-#### Inspection requested via web by Terissa Morain

Final ok
ELE20-01283 Rough-In Permanent Service4/24/20204/27/20204/27/2020 10:05:13 AMAFAIL
Lock box code is 7326. Rough in inspection for house, detached garage and underground conduit going from service to detached garage. Call Caleb with any questions or concerns. Phone #: ###-#### Inspection requested via web by Caleb Gaylord
210.70 Lighting switch required at stair level
330 Bored holes closer then 1 1/4 shall be protected with a listed nailplates
334 Type NM cable shall be protected from physical damage(going down stairs)