Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00056 FIR-Aging Inspection4/28/20044/28/20044/28/2004 12:00:00 AM NR
Per rod walters with simplexgrinnell they are waiting for the owner to provide electrical shutdown for the cooking appliances. 4/28/2004 3:19:37 PM
FIR03-00750 INSP-Final Inspection4/28/20044/28/20044/28/2004 12:00:00 AMAPASS
fire alarm finaled
MIS04-00119 FIR-Final4/26/20044/28/20044/28/2004 12:00:00 AMAPART
A temporary occupancy was given until items on the correction notice have been corrected.. Itemse include providing "Door to remain unlocked while building is occupied" sticker at main exit, remove manual flush bolts at main exit and at the rear exit, provide approved door hardware at the rear exit, provide exit signs and emergency lights as discussed and per plan (one at low wall not required), provide fire extinguisher with current inspection tag and mounted at 48" 4/28/2004 9:20:35 AM
MIS04-00105 FIR-Final4/27/20044/28/20044/28/2004 12:00:00 AMAPASS
Life safety finaled 4/28/2004 8:23:10 AM
BLD03-01851 FIRE-Final Inspection4/27/20044/28/20044/28/2004 12:00:00 AMAFAIL
Relocate emergency light at the south entry. Add an emergency light in the long corridor. Paint fire dept. access as discussed. Provide correct sticker at the main entry exits. Provide approved door hardware on doors 130-1 and 130-2 per plan review note #48. Provide additional permits for the tenants. 4/28/2004 1:54:20 PM
FIR04-00247 INSP-Sprinkler Rough-in/Hydro4/27/20044/28/20044/28/2004 12:00:00 AMAFAIL
two existing pendants are piped from the same outlet in back corridor/telephone room. Provide separate supply or calculations 4/28/2004 9:46:55 AM
BLD03-02844 FIRE-Final Inspection4/27/20044/28/20044/28/2004 12:00:00 AMAFAIL
Provide approved drawings for the fire sprinkler final. Remove thumbturns from the class room doors (total of 3), Repair exit signs neare womens restroom, computer lab and the two on the second floor, Repair exit sign outside of the kitchen, provide emergency light in main corridor, basement, basement stairs and outside of the kitchen, Repair the emergency light at the womens restroom, Repair emergency light/exit sign in classroom 141. 4/28/2004 11:45:45 AM
FIR04-00165 INSP-Final Inspection4/27/20044/28/20044/28/2004 12:00:00 AMPCANC
Inspection performed for FIR04-00213 4/28/2004 3:17:02 PM
FIR04-00247 INSP-Sprinkler Rough-in/Hydro4/28/20044/28/20044/28/2004 12:00:00 AMPPASS
Need ceiling tile and canopies on pendants 4/28/2004 3:30:07 PM
BLD04-00222 FIRE-Final Inspection4/28/20044/28/20044/28/2004 12:00:00 AMPFAIL
Provide fire alarm plans. Provide address. Provide exit sign at the storage room exit. Mount the additional fire extinguisher as discussed. Remove the manual flush bolts at the main entry/exit. Remove hardware from the second entry/exit.
FIR04-00213 INSP-Final Inspection4/28/20044/28/20044/28/2004 12:00:00 AMPFAIL
Provide canopies on the sprinkler pendants. Insulation is still blocking sprinkler upright coverage in three locations. Provide annual inspection for the existing sprinkler system.
BLD03-02790 FIRE-Final Inspection4/27/20044/28/20044/27/2004 3:44:27 PMACANC
Joe; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Inspection cancelled from web by: Aimee Hughes