Inspections for the day of: Friday, April 28, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01479 Temporary Service4/28/20064/28/20064/28/2006 4:17:10 PMPFAIL
ted- ###-#### t/p called contr, left corr notice, 312.5 all conductors entering enclosures shall have abrasion protection, 310.7 conductors used for dierct burial shall be of a type identified for such use, 250.20 gec shall be connected, 250.24(A) gec shall be connected to grounded conductor terminal, BCC job id sticker shall be posted
ELE06-01155 Rough-In Permanent Service4/28/20064/28/20064/28/2006 3:48:54 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla called contr, left corr notice, nec 300.4(A)(1) edge of bored holes shall be 1 1/4" from edge of framing members, 314.20 box in combustible material shall be flush with finished surface, BCC all make-up shall be done, Note contractor to change permit to 17 rooms.
ELE06-00113 Electrical Rough-In4/27/20064/28/20064/28/2006 2:55:38 PMPPART
greg//ri on the 9th floor; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa walls anop ok to cover, 9th fl
ELE06-00520 Final4/28/20064/28/20064/28/2006 1:30:45 PMPFAIL
paul ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr, left corr notice, 210.52(C)(2) recpt shall be installed in counter space by sink, 404.4 switch shall not be installed in tub space, 406.4(D) recpt shall be flush or project from faceplate, 406.4 recpt shall be securely fastened in place
ELE06-00753 Final4/28/20064/28/20064/28/2006 12:54:23 PMPPASS
scott; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
ELE06-01468 Final4/27/20064/28/20064/28/2006 11:41:52 AMAPASS
We ran a new 20 amp 120 volt circuit from the indoor panel to a new weather proof bell box on the back of the house, then ran IMC from it thru the trench to a new GFCI receptacle in the shed in the back yard.Thanks!!!!; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to final
ELE06-00687 Final4/27/20064/28/20064/28/2006 10:32:16 AMAFAIL
called contr, left corr notice,nec 410.8(C) partially enclosed lamps shall not be permitted in clothes closet, 110.12(A) unused openings in boxes shall be closed,334.30 nm cable shall be supported eithin 12" of box, 210.8)A)(1) gfci shall be installed in bathroom
ELE06-01442 Electrical Rough-In4/26/20064/28/20064/28/2006 10:20:34 AMAPASS
###-#### - STEPHEN ric ok
ELE06-01442 Permanent Service4/28/20064/28/20064/28/2006 10:19:55 AMAPASS
p/s u/g n ok
ELE06-01452 Electrical Rough-In4/27/20064/28/20064/28/2006 10:17:35 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook ri walls only ok to cover and parapets
ELE06-01471 Final4/27/20064/28/20064/28/2006 9:35:37 AMAPASS
###-#### - stu called contr to add ko seal id panel, ok to final
ELE06-01461 Final4/27/20064/28/20064/28/2006 8:46:58 AMACANC
###-#### - kelly called contr, no address, no job id sticker, no tlr tag for service rating, no gec abrasion prot