BLD03-01845
| FIRE-Final Inspection | 4/24/2006 | 4/24/2006 | | A | |
|
|
For final status
|
FIR05-00846
| INSP-Final Inspection | 4/27/2006 | 4/28/2006 | 5/1/2006 2:02:35 PM | A | PART |
|
|
On site confrence to determine hydrostatic testing requirements.
|
BLD05-02482
| FIRE-Final Inspection | 4/28/2006 | 4/28/2006 | 4/28/2006 4:04:00 PM | P | FAIL |
|
|
Project is not in condition for a final life safety inspection, missing doors, hardware, need to provide approved building address, stair hand rails are not installed, need to test emergency lighting etc.
|
FIR06-00128
| INSP-Sprinkler Rough-in/Hydro | 4/27/2006 | 4/28/2006 | 4/28/2006 3:23:44 PM | P | PART |
|
|
Inspection for cover at the hard lid restrooms in the basement, noted one hanger ring to be changed at an arm over.
|
FIR06-00276
| INSP-Final Inspection | 4/28/2006 | 4/28/2006 | 4/28/2006 1:22:00 PM | P | PART |
|
|
Overhead sprinkler work is good for cover at the drop ceiling areas, will need to install ceiling tile and escutcheons and verify existing system is current with an annual inspection tag prior to final.
|
BLD04-02348
| FIRE-Final Inspection | 4/27/2006 | 4/28/2006 | 4/28/2006 12:31:02 PM | A | PASS |
|
|
Correction notice items have been completed as required, fire life safety is satisfactory, the two doors at the stairway exit discharge ground level shall be verified to meet opening force requirements per IFC 2003 at structural final inspection.
|
FIR05-00449
| INSP-Final Inspection | 4/28/2006 | 4/28/2006 | 4/28/2006 12:26:38 PM | P | PASS |
|
|
Added devices at the top of elevator hoistway tested, updated map verified, covers at SD removed, alarm passed final field inspection, permit finaled.
|
FIR05-00594
| INSP-Final Inspection | 4/28/2006 | 4/28/2006 | 4/28/2006 12:23:37 PM | P | PASS |
|
|
Fire sprinkler passed final inspection, permit finaled.
|
FIR06-00112
| INSP-Final Inspection | 4/27/2006 | 4/28/2006 | 4/28/2006 9:43:54 AM | A | FAIL |
|
|
Tested notification and detection devices at the 10th and 11th floor machine rooms, helipad, elevator lobbies, mech. penthouse, tested manual pulls, smoke at nac panel, tested sprinkler tampers and flows at the 10th floor manifold. The notification devices at the north mech. penthouse 3rd floor failed to function properly, need to test sprinkler tampers and flows at the 4th floor and tamper at the 3rd floor at next inspection.
|