Inspections for the day of: Monday, April 28, 2008.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00166 INSP-Final Inspection4/28/20084/28/20084/29/2008 5:26:48 PMPPASS
Fire alarm permit work scope is approved for final-some locations eclipsed by subsequent tenant fire alarm modifications inspected under respective permits for the 5th and 4th floors.
FIR07-00137 INSP-Final Inspection4/28/20084/28/20084/28/2008 3:48:39 PMPPASS
Fire alarm modifications passed final inspection per site visit completed 5/3/07, permit finaled.
FIR08-00180 INSP-Sprinkler Rough-in/Hydro4/25/20084/28/20084/28/2008 3:43:33 PMPFAIL
Hydrostatic testing for the new 10" supply line failed due to pressure loss at the guage and visible leakage at OS&Y isolation valves, also noted system static is approx. 165 psi which will necessitate testing in excess of 200 psi to meet NFPA requirements.
FIR06-00621 INSP-Alarm Testing4/23/20084/28/20084/28/2008 3:39:27 PMAPART
Completed preliminary walkthrough of cleanroom areas prior to fire alarm notification test to verify positioning, cd settings and spacing of horn/strobe appliances.
FIR06-00620 INSP-Alarm Testing4/23/20084/28/20084/28/2008 3:38:46 PMAPART
Completed preliminary walkthrough of cleanroom areas prior to fire alarm notification test to verify positioning, cd settings and spacing of horn/strobe appliances.
BLD07-01757 FIRE-Final Inspection4/25/20084/28/20084/28/2008 11:30:11 AMAPASS
Fire life safety inspection completed satisfactory, door closure at two locations including doors170-2 at the Cultural Hall and 168-1at room 168 south side are in need of adjustment- this is to be completed prior to structural final and verified at that time as discussed.
FIR08-00241 INSP-Final Inspection4/25/20084/28/20084/28/2008 11:26:32 AMAPASS
Noted correction at the previous inspection verified for completion, new fire alarm work passed field testing, permit finaled.
FIR07-00902 INSP-Sprinkler Rough-in/Hydro4/28/20084/28/20084/28/2008 10:25:31 AMAPART
See locatons on approved plans set for rough-in areas inspected and okayed to date, noted shell protection sprig-ups at the common corridor 2nd floor are not installed-heads at this area may coincide with tenant permit work depending on job schedule.