BLD08-00981
| BLD-Aging Inspection | 4/28/2009 | 4/28/2009 | 4/29/2009 3:04:54 PM | | PASS |
|
|
This tenant is no longer in this tenant space. There is construction currently going on for another tenant.
|
FIR07-00874
| INSP-Final Inspection | 4/28/2009 | 4/28/2009 | 4/28/2009 4:21:22 PM | P | PASS |
|
|
permit finaled
|
FIR08-00832
| INSP-Sprinkler Rough-in/Hydro | 4/27/2009 | 4/28/2009 | 4/28/2009 3:59:37 PM | A | PART |
|
|
Todays inspection covered building "C" first and second floors. The sidewall sprinkler heads provided under the exterior canopies are wrong and the correct ones will need to be installed. Pipe sizing and hangers appear to be correct. One additional sidewall has been added under a southwest exterior canopy. Sprinkler piping can't be covered until the insulation has been inspected. Also the pendant heads in the corridors have not been cut in yet.
|
FIR08-00844
| FIR-Aging Inspection | 4/28/2009 | 4/28/2009 | 4/28/2009 3:47:22 PM | | NR |
|
|
Work is in progress.
|
FIR08-00787
| INSP-Final Inspection | 4/27/2009 | 4/28/2009 | 4/28/2009 3:45:33 PM | P | PASS |
|
|
Permit finaled
|
FIR07-00874
| INSP-Final Inspection | 4/27/2009 | 4/28/2009 | 4/28/2009 3:44:57 PM | A | PASS |
|
|
Permit finaled
|
BLD07-01845
| FIRE-Final Inspection | 4/27/2009 | 4/28/2009 | 4/28/2009 3:41:53 PM | A | PART |
|
|
A temporary occupancy was given for the remaining assisted living area. See the city approved resubmittals for the two exit signs that need to be provided and the two emergency lights that need added. Also the project related fire alarm permit needs finaled.
|
FIR08-00094
| INSP-Alarm Testing | 4/27/2009 | 4/28/2009 | 4/28/2009 3:40:09 PM | A | PASS |
|
|
The alarm system for the remaining area of the Assisted Living is complete. Resubmittals are required showing all of the changes which include wall layout changes. Robert will provide a printout of the test reports.
|
BLD09-00436
| FIRE-Final Inspection | 4/27/2009 | 4/28/2009 | 4/28/2009 10:05:48 AM | A | PASS |
|
|
life safety passed
|