Inspections for the day of: Wednesday, April 28, 2010.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00728 INSP-Final Inspection4/28/20104/28/20104/28/2010 3:54:24 PMPFAIL
Plans need to be resubmitted showing the wall layout changes which will require additional notification device/devices. Several smoke and heat detectors were located less than 3' from supply registers. One strobe on the second level was not set at the correct candella and was corrected while on site. Voltage drops were verified for both of the notification circuits and both circuits checked out ok. The Netcon was verified at a 5 multiple times. All other notication device locations are approved except as noted above due to wall changes.
FIR10-00138 INSP-Final Inspection4/27/20104/28/20104/28/2010 3:24:10 PMPFAIL
All items are ok except that the two remote test switches have apparently been left above the ceiling. Once their installation has been verified this permit can be finaled.
FIR10-00129 INSP-Final Inspection4/28/20104/28/20104/28/2010 1:56:13 PMPPASS
Permit finaled.
BLD10-00360 FIRE-Final Inspection4/26/20104/28/20104/28/2010 1:53:58 PMPFAIL
Life safety will be ok to pass when the project related fire alarm permit is finaled.
BLD09-02089 FIRE-Final Inspection4/27/20104/28/20104/28/2010 9:51:11 AMAPASS
life safety passed
FIR10-00050 INSP-Final Inspection4/27/20104/28/20104/28/2010 9:22:36 AMAPASS
Permit finaled
FIR10-00138 INSP-Final Inspection4/26/20104/28/20104/27/2010 10:47:28 AMACANC
Troy, Please let us know an approximate time, so we can let everyone know. Thanks. Jason ###-#### Inspection requested from web by: Jason Minnick Phone #: ###-#### Inspection cancelled from web by: Jason Minnick