ELE12-00661
| ELE-Aging Inspection | 4/28/2014 | 4/28/2014 | 4/28/2014 4:08:54 PM | | DONE |
|
|
Drove by posted correction
|
ELE14-00672
| Final | 4/28/2014 | 4/28/2014 | 4/28/2014 3:28:29 PM | P | PASS |
|
|
Rock
If you go to the front desk they can get you into the exercise room and the ada room #119 I think is the number. The newly remodled bath room. Thanks Mike Phone #: ###-#### >> Inspection requested via web by Mike Cole Final ok
|
ELE14-01044
| Final | 4/28/2014 | 4/28/2014 | 4/28/2014 2:45:39 PM | P | FAIL |
|
|
Garage wired. I will leave the back door open. Phone #: ###-#### >> Inspection requested via web by Greg Idsinga 406.11-In all areas specified in 210.52, all 120 volt 15 and 20 amp receptical outlets shall be listed tamper resistant recepticals. Garages included
|
ELE14-01050
| Permanent Service | 4/28/2014 | 4/28/2014 | 4/28/2014 2:18:43 PM | P | PART |
|
|
The new service is on the East side of the garage. There is also a new panel on the Sout side of the house by the hot tub. 250.32- grounding electrode system shall be established at rmote building (house). Main service rough in ok. p/s u/g n ok
Please call when you are on the way so that the owner can be advised that you will be on site. Phone #: ###-#### >> Inspection requested via web by Spencer McLean
|
ELE14-00636
| Electrical Rough-In | 4/28/2014 | 4/28/2014 | 4/28/2014 1:22:10 PM | P | PASS |
|
|
Trenching/conduit//Please call ahead for access- casey Phone #: ###-#### Tamper resistant recepticals required and access for concrete encased electrode. Rough in ok cover
|
ELE14-01046
| Rough-In Permanent Service | 4/28/2014 | 4/28/2014 | 4/28/2014 12:29:49 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI Rough in ok cover p/s u/g n ok
|
ELE14-01024
| Conference | 4/24/2014 | 4/28/2014 | 4/28/2014 9:55:49 AM | A | DONE |
|
|
Robert ###-#### Discussed GFCI protection of kitchen receptical outlets, AFCI protection of all bedroom outlets, establish ground at detached garage, abrasion protection at junction boxes in garage. All wires fished in walls. Basement ceiling rough in ok cover
|