Inspections for the day of: Thursday, April 28, 2016.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01498 ELE-Aging Inspection4/28/20164/28/20164/29/2016 4:17:32 PM CANC
ELE16-01327 Electrical Rough-In4/27/20164/28/20164/28/2016 4:16:16 PMPPASS
Added floor boxes in 3 rooms need underground inspection for pour back Friday. Phone #: ###-#### Inspection requested via web by Tyler Bowen
Called to check if permit is to cover full remodel of building or just lighting retro. Steve called from RME and informed office will addwork to this permit or pull another. Underslab for conference rm, break rm, and training rm rough in ok cover
ELE16-01231 Final4/28/20164/28/20164/28/2016 3:56:25 PMPFAIL
Please contact homeowner Vern Ricketts at ###-#### for access. Thanks Phone #: ###-#### Inspection requested via web by steve ragan
408.4- Circuit directory shall be complete.
342.30- INC service riser shall be secured with in 3' of meter.
Owner informed of additional receptacles will be added in garage.
ELE16-00868 Final4/28/20164/28/20164/28/2016 3:11:21 PMPFAIL
Please make this inspection as late as possible today. Daven Story on site.....###-#### Phone #: ###-#### Inspection requested via web by Brian Caruso
Handle tie for 2-pole for AC.
Service receptacle for AC.
GFCI protect receptacle with in 6' of mop sink.
ELE16-01064 Final4/27/20164/28/20164/28/2016 2:16:47 PMPPASS
Final Inspection Phone #: ###-#### Inspection requested via web by Christy Cheney Final ok
ELE16-01164 Final4/28/20164/28/20164/28/2016 1:46:18 PMPPASS
Homeowner Dan
###-#### Phone #: ###-#### Inspection requested via web by Emmet Bushman Final ok
ESC16-00251 General Inspection4/28/20164/28/20164/28/2016 1:28:07 PMPPASS
All waste contained. OK
ELE16-01330 Rough-In Permanent Service4/27/20164/28/20164/28/2016 1:11:43 PMPPASS
Phone #: ###-#### Inspection requested via web by Randy Fletcher
house unoccupied. Sub-feeds not in at time of inspection. Asked to remove all NM cable under deck due to damp location and remove flexible cord feeding garage door opener. p/s u/g n ok
ELE16-01003 Final4/28/20164/28/20164/28/2016 12:34:22 PMPNR
Please call Dan at ###-#### half an hour before arrival and he will meet you there. Thank you! Phone #: ###-#### Inspection requested via web by Dan Mitchell
Labels not complete
ELE16-01003 Electrical Rough-In4/28/20164/28/20164/28/2016 12:33:27 PMPPASS
Please call Dan at ###-#### half an hour before arrival and he will meet you there. Thank you! Phone #: ###-#### Inspection requested via web by Dan Mitchell
Service rough in ok cover
ELE16-01003 Permanent Service4/28/20164/28/20164/28/2016 12:32:39 PMPPASS
Please call Dan at ###-#### half an hour before arrival and he will meet you there. Thank you! Phone #: ###-#### Inspection requested via web by Dan Mitchell
Corrections and testing complete.
p/s u/g n ok
ELE15-03169 Electrical Rough-In4/28/20164/28/20164/28/2016 9:56:17 AMAPASS
rough in Leds sanctuary. We will arrive approx 9am. Phone #: ###-#### Inspection requested via web by Tim Dunlop
At this time only doing listed LED cans retro trims in sanctuary. Rough in ok
ELE16-01265 Electrical Rough-In4/27/20164/28/20164/28/2016 9:21:39 AMAPASS
Phone #: ###-#### Inspection requested via web by CHRIS CARMINE
Perimeter bond, ladder, dive board, potting rough in ok cover
ELE16-00539 Final4/27/20164/28/20164/28/2016 8:55:59 AMAPASS
Code is 0500 Phone #: ###-#### Inspection requested via web by TOM BICANDI Final ok
ELE16-01334 Electrical Rough-In4/27/20164/28/20164/28/2016 8:13:03 AMPCANC
Wall rough-in please. Contact will be David Joseph ###-####. Please give him a call if you have any questions as he will not be on site. Thank you and have a super day! Phone #: ###-#### >> Inspection requested via web by Laura Longshaw Inspection cancelled from web by: Laura Longshaw
ELE16-01195 Final4/27/20164/28/20164/28/2016 8:07:09 AMAPASS
Paul. Lock box code is 3701 corrections made. Phone #: ###-#### Inspection requested via web by Sean DeLacy
Final ok