Inspections for the day of: Thursday, April 28, 2016.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-02530 FIRE-Final Inspection4/28/20164/28/20164/28/2016 4:02:10 PMPFAIL
None of the exit signs/emergency lighting/discharge landing illumination located in the west section storage unit corridors could be verified for proper operation, there was tripped circuit breaker on lighting circuit and emergency power source was depleted, all exit lighting/emergency egress needs to be operable at time of final inspection. Discharge landing illumination needs to be tested/verified for proper operation , interior emergency lighting on these fixtures were operable when AC power source was isolated, multiple lights on discharge landings did not illuminate, inoperable discharge landing lights need to be repaired and operating at time of final inspection.
BLD15-02657 FIRE-Final Inspection4/28/20164/28/20164/28/2016 3:55:01 PMPFAIL
Exit sign needs to be installed showing egress path of travel at small corridor between the main corridors, middle of building, same area is missing emergency egress light fixture, light needs to be installed. Exit sign in east storage by unit 2108 did not stay illuminated on emergency power, exit sign needs repaired. Discharge landing illumination needs to be tested/verified for proper operation , interior emergency lighting on these fixtures were operable when AC power source was isolated, multiple lights on discharge landings did not illuminate, inoperable discharge landing lights need to be repaired and operating at time of final inspection.
BLD16-00868 FIRE-Final Inspection4/28/20164/28/20164/28/2016 2:43:38 PMPPART
Partial life fire safety inspection complete, area of work (new wall/exit signs) pass for life fire safety, fire extinguishers are in place with current inspection tags. Fire sprinkler heads next to area of work are spaced to close together, fire sprinkler heads need to be relocated for proper spacing, in same area there is a fire sprinkler head spaced to far off of wall, head needs to be relocated for proper spacing of fire sprinklers. After fire sprinklers have been repaired and passed final inspection this permit can be finaled for life fire safety.
BLD15-04047 FIRE-Final Inspection4/28/20164/28/20164/28/2016 1:47:02 PMPPASS
No fire sprinklers, no fire alarms, fire extinguisher is in place with a current inspection tag, compressed gas tanks are chanined and secure. Tenant space has round type door hardware on all doors as well as thumb-turn deadbolts on some of the interior doors of space, does not appear that any upgrading has been made on doors/door hardware so existing door hardware was accepted. Final life fire safety inspection passed/complete.
FIR16-00129 INSP-Sprinkler Rough-in4/28/20164/28/20164/28/2016 12:26:11 PMPPART
Notated gridded area's approved for cover on the city approved drawings with blue highlighter. Area's marked are approved for cover.
FIR16-00106 INSP-Sprinkler Rough-in/Hydro4/26/20164/28/20164/28/2016 11:44:54 AMPCANC
Call Jake when you are heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
FIR16-00195 INSP-Final Inspection4/27/20164/28/20164/28/2016 10:37:35 AMACANC
Inspection request cancelled per conversation with point of contact, Peter Phone #: ###-####. Inspection request will be rescheduled for later date.
FIR15-00806 INSP-Sprinkler Rough-in/Hydro4/27/20164/28/20164/28/2016 10:26:24 AMPCANC
Inspection request cancelled by point of contact on project, tenting insulation will not be complete by the time inspection can be done, inspection request will be rescheduled after insulation is complete