Inspections for the day of: Friday, April 28, 2017.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC16-05365 Final4/28/20174/28/20174/28/2017 4:12:37 PMPFAIL
flue wont hold pressure
MEC17-01274 Rough-in4/26/20174/28/20174/28/2017 3:46:40 PMPPASS
Phone #: ###-#### Inspection requested via web by Lisa Whitney
MEC17-01274 Pressure Test4/26/20174/28/20174/28/2017 3:45:09 PMPPART
Phone #: ###-#### Inspection requested via web by Lisa Whitney- 60 lb gas pass- 20lb gas fail- 5lb flue to furnace fail- 5lb flue to water heater pass
MEC17-01473 Rough-in4/28/20174/28/20174/28/2017 3:27:32 PMPPASS
Phone #: ###-#### Inspection requested via web by Dan Otero
MEC17-01553 Final4/28/20174/28/20174/28/2017 3:05:31 PMPPASS
ready please call Josh ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss
MEC17-01472 Rough-in4/28/20174/28/20174/28/2017 2:37:19 PMPPASS
Phone #: ###-#### Inspection requested via web by Dan Otero
MEC17-01544 Conference4/27/20174/28/20174/28/2017 2:20:41 PMPDONE
would like call ahead; Brian Phone #: ###-####-
MEC17-01551 Final4/28/20174/28/20174/28/2017 2:09:03 PMPPASS
ready please call Craig ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss
MEC16-04971 Final4/28/20174/28/20174/28/2017 1:49:36 PMPPART
Contact Antonio ###-####
Kevin will have TAB report and the building flush is starting today. Phone #: ###-#### Inspection requested via web by Dan Flaherty- 3 bvents for tube heaters exhaust side need clearance to combustibles at roof penetrations- talked with Antonio about this- temp occupancy ok
MEC16-01382 Mec-Aging Inspection4/28/20174/28/20174/28/2017 11:27:28 AM CANC
no calls
MEC17-00427 Rough-in4/27/20174/28/20174/28/2017 11:19:29 AMAPASS
MARC IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER- 2nd floor hydronics 100lb pressure test pass-- ok to insulate-
MEC17-01531 Rough-in4/27/20174/28/20174/28/2017 10:46:55 AMAFAIL
r/i and p/t -- (man J on wall at top of stairs) - Will Phone #: ###-####- approved manual J onsite does not have duct routing pages in it- 2' flue test fail- guage below 5 psi
MEC17-01531 Pressure Test4/28/20174/28/20174/28/2017 10:45:41 AMAPART
20lb gas pass- 5lb flue 3" pass- 2" flue fail guage below 5 psi
MEC17-01527 Final4/27/20174/28/20174/28/2017 10:25:18 AMAPASS
Phone #: ###-#### Inspection requested via web by Dan Otero
MEC17-01474 Final4/25/20174/28/20174/28/2017 9:21:29 AMAPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette
MEC17-01545 Final4/27/20174/28/20174/28/2017 8:33:27 AMAPASS
Phone #: ###-#### Inspection requested via web by Xanti Berria
MEC16-01388 Mec-Aging Inspection4/28/20174/28/20174/28/2017 8:18:18 AM FAIL
no calls
MEC15-06041 Mec-Aging Inspection4/28/20174/28/20174/28/2017 8:17:09 AM CANC
no calls