ELE04-01520 Final4/28/20054/29/20054/29/2005 12:00:00 AMANR
any questions please call Tim Watkins; Phone #: ###-#### Internet Inspection Request from: Jeff Radford met elect, he needs to change the main breaker and provide gfci protection for 120 v recpts. Did not open panel, needs to be looked at. 1 leg of 220 v service has been abandoned, therefore service needs to be 120v 1 phase. 4/29/2005 3:04:24 PM
ELE05-00818 Final4/28/20054/29/20054/29/2005 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 4/28/2005 at 1:52:13 PM. Contact: ###-####. corrections made, ok to final 4/29/2005 8:00:53 AM
ELE04-03683 Temporary Service4/28/20054/29/20054/29/2005 12:00:00 AMACANC
Scheduled by a contractor via Hello! on 4/28/2005 at 2:54:31 PM. Contact: ###-####. see added inspection 4/29/2005 9:01:56 AM
ELE05-01472 Rough-In Permanent Service4/28/20054/29/20054/29/2005 12:00:00 AMAPASS
brandon ###-#### ric ok, p/s u/g n ok 4/29/2005 8:12:51 AM
ELE05-01194 Final4/28/20054/29/20054/29/2005 12:00:00 AMAPASS
DOUG; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to final, signed occupancy card 4/29/2005 9:53:09 AM
ELE05-01452 Permanent Service4/29/20054/29/20054/29/2005 12:00:00 AMADONE
Scheduled by a contractor via Hello! on 4/29/2005 at 7:02:29 AM. Contact: ###-####. 4/29/2005 9:18:49 AM
ELE05-01410 Permanent Service4/29/20054/29/20054/29/2005 12:00:00 AMACANC
Scheduled by a contractor via Hello! on 4/29/2005 at 7:03:56 AM. Contact: ###-####. wrong address 4/29/2005 9:15:20 AM
ELE05-01475 Final4/29/20054/29/20054/29/2005 12:00:00 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok to final 4/29/2005 11:07:26 AM
ELE05-01463 Rough-In Permanent Service4/28/20054/29/20054/29/2005 12:00:00 AMAPASS
###-#### dino ric ok p/s u/g n ok 4/29/2005 9:45:57 AM
ELE05-01464 Electrical Rough-In4/28/20054/29/20054/29/2005 12:00:00 AMAFAIL
###-#### Verna 4/29/2005 8:14:56 AM called contr, left message, left corr notice, 314.20 boxes shall be flush with surface on outside walls, 210.52(D) recpt shall be within 3' of basin upstairs bath, BCC job id shall be posted 4/29/2005 8:17:20 AM
ELE04-03683 Permanent Service4/29/20054/29/20054/29/2005 12:00:00 AMAPASS
p/s u/g n ok
ELE05-01411 Permanent Service4/29/20054/29/20054/29/2005 12:00:00 AMAPASS
p/s u/g n ok
ELE05-00422 Final4/29/20054/29/20054/29/2005 12:00:00 AMPPASS
deno ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok to final 4/29/2005 4:29:35 PM
ELE05-00739 Final4/29/20054/29/20054/29/2005 12:00:00 AMPPART
STEVE FINAL; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy will finish with core and shell, need to sign occupancy card 4/29/2005 1:12:46 PM
ELE05-01467 Permanent Service4/28/20054/29/20054/29/2005 12:00:00 AMPPASS
p/s u/g exst ok 4/29/2005 1:11:18 PM
ELE05-00961 Final4/29/20054/29/20054/29/2005 12:00:00 AMPPASS
darrell; Phone #: ###-#### Internet Inspection Request from: Barbara Moore talked to contr, ok to final 4/29/2005 2:08:23 PM
ELE05-01424 Electrical Rough-In4/29/20054/29/20054/29/2005 12:00:00 AMPCANC
any questions please call Ed Schallock; Phone #: ###-#### Internet Inspection Request from: Jeff Radford wrong call, really t/s 4/29/2005 3:59:42 PM
ELE05-01424 Temporary Service4/29/20054/29/20054/29/2005 12:00:00 AMPPASS
any questions please give Ed Schallock a call; Phone #: ###-#### Internet Inspection Request from: Jeff Radford t/s u/g n ok 4/29/2005 2:55:33 PM
ELE05-01326 Final4/27/20054/29/20054/28/2005 11:50:39 AMACANC
rick; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Disp set to [CANC] by a contractor via Hello! on Apr 28 2005 11:50AM.
ELE05-00010 Final4/22/20054/29/20054/28/2005 10:42:53 AMPCANC
We installed a new 20 amp 120 volt circuit to a new receptacle for the above-the-range microwave.Thanks!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell Inspection cancelled from web by: Dan Mitchell