Inspections for the day of: Friday, April 29, 2005.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-00102 FIRE-Final Inspection4/29/20054/29/20054/29/2005 3:46:52 PMPCANC
Contact: ###-####. One of the fire sprinkler permits shows in review status. No inspection done
FIR04-00708 INSP-Final Inspection4/28/20054/29/20054/29/2005 3:42:11 PMPPASS
Hood suppression system operated correctly
FIR04-00730 INSP-Final Inspection4/28/20054/29/20054/29/2005 3:40:55 PMPCANC
lynda; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
FIR05-00157 INSP-Final Inspection4/27/20054/29/20054/29/2005 3:08:12 PMPFAIL
Can't give final ok until ceiling tile has been installed at the sprinkler pendants. Sprinkler piping is ok to cover.
BLD05-00327 FIRE-Final Inspection4/28/20054/29/20054/29/2005 2:36:09 PMAPART
A temporary occupancy was given with Dave Lokker's permission. A fire extinguisher needs tagged and the main exit and the common use restroom doors do not meet requirement number 1 of the IFC Access Controlled Egress Doors - (exit sensor). I spoke with Li
FIR05-00233 INSP-Final Inspection4/28/20054/29/20054/29/2005 2:19:02 PMPPASS
Fire alarm finaled
BLD03-01020 FIRE-Final Inspection4/28/20054/29/20054/29/2005 1:51:33 PMAFAIL
Contact: ###-####. Inspection was a conference to see what items are needed for a final. Dennis is to provide verification that min control valve for the fire sprinkler system is monitored by the fire alarm system
FIR04-00656 INSP-Sprinkler Rough-in/Hydro4/28/20054/29/20054/29/2005 1:43:36 PMAPART
Inspection was for above ground hydro test. All passed except for the second, third and fourth floors. Third and fourth floors fed from same riser
FIR05-00250 INSP-Final Inspection4/28/20054/29/20054/29/2005 11:28:51 AMAPASS
Fire sprinkler finaled
FIR05-00230 INSP-Final Inspection4/28/20054/29/20054/29/2005 10:57:41 AMAPASS
Fire alarm finaled
BLD05-00470 FIRE-Final Inspection4/28/20054/29/20054/29/2005 9:47:32 AMAPASS
Fire life safety finaled
FIR05-00246 INSP-Final Inspection4/28/20054/29/20054/29/2005 9:45:46 AMPPASS
Fire alarm finaled
BLD03-02531 FIRE-Final Inspection4/28/20054/29/20054/29/2005 9:08:22 AMAFAIL
ted; Phone #: ###-#### Need approved plans for inspection, doors in common stairwells did not self close, smoke detectors in corridor are within 20 feet of the cooking appliances so it'll need self silencing or be of photo electric type, need text paint
BLD03-02530 FIRE-Final Inspection4/28/20054/29/20054/29/2005 9:07:55 AMAFAIL
ted; Phone #: ###-#### Need approved plans for inspection, doors in common stairwells did not self close, smoke detectors in corridor are within 20 feet of the cooking appliances so it'll need self silencing or be of photo electric type, need text paint
BLD03-02528 FIRE-Final Inspection4/28/20054/29/20054/29/2005 9:07:20 AMAFAIL
ted; Phone #: ###-#### Need approved plans for inspection, doors in common stairwells did not self close, smoke detectors in corridor are within 20 feet of the cooking appliances so it'll need self silencing or be of photo electric type, need text paint
BLD03-02529 FIRE-Final Inspection4/28/20054/29/20054/29/2005 9:06:54 AMAFAIL
ted; Phone #: ###-#### Need approved plans for inspection, doors in common stairwells did not self close, smoke detectors in corridor are within 20 feet of the cooking appliances so it'll need self silencing or be of photo electric type, need text paint
BLD03-02527 FIRE-Final Inspection4/28/20054/29/20054/29/2005 9:06:32 AMAFAIL
ted; Phone #: ###-#### Need approved plans for inspection, doors in common stairwells did not self close, smoke detectors in corridor are within 20 feet of the cooking appliances so it'll need self silencing or be of photo electric type, need text paint
BLD03-02526 FIRE-Final Inspection4/28/20054/29/20054/29/2005 9:06:09 AMAFAIL
ted; Phone #: ###-#### Need approved plans for inspection, doors in common stairwells did not self close, smoke detectors in corridor are within 20 feet of the cooking appliances so it'll need self silencing or be of photo electric type, need text paint
BLD05-00844 FIRE-Final Inspection4/28/20054/29/20054/29/2005 7:39:55 AMAPASS
fire life safety finaled
BLD04-02558 FIRE-Final Inspection4/29/20054/29/20054/29/2005 12:00:00 AMPPART
A temporary occupancy was given with Dave Lokkers permission until the interconnect between the spraying equipment and the fan has been completed. Owner was going to mount the signs after I left. Will verify when I return.