FIR08-00129
| INSP-Final Inspection | 4/28/2008 | 4/29/2008 | 4/30/2008 2:27:18 PM | A | NR |
|
|
Work is not ready for inspection per conversation with contractor.
|
BLD07-02078
| FIRE-Conference | 4/29/2008 | 4/29/2008 | 4/29/2008 5:23:15 PM | P | DONE |
|
|
Work in progress
|
FIR08-00180
| INSP-Sprinkler Rough-in/Hydro | 4/29/2008 | 4/29/2008 | 4/29/2008 5:22:48 PM | A | NR |
|
|
New supply line pipe hydrostatic test is not ready for inspection due to leakage per contractor, also okayed areas as red-lined on approved plan set at the front office entry hard lids-noted three ret. straps to be attatched and one head to be relocated for correct min. spacing requirements.
|
FIR08-00130
| INSP-Sprinkler Rough-in | 4/28/2008 | 4/29/2008 | 4/29/2008 1:22:20 PM | A | PART |
|
|
Approved overhead rough-in at all areas except as noted in two locations including a missed head and one branch line arm-over to be re-routed due to excessive pipe deflection radius. Cold cavity tenting appears satisfactory.
|
FIR06-00621
| INSP-Alarm Testing | 4/23/2008 | 4/29/2008 | 4/29/2008 1:18:04 PM | A | PART |
|
|
Horn and strobe testing completed for the cleanroom areas only, noted locations on plan in need of revision.
|
FIR06-00620
| INSP-Alarm Testing | 4/23/2008 | 4/29/2008 | 4/29/2008 1:17:31 PM | A | PART |
|
|
Horn and strobe testing completed for the cleanroom areas only, noted locations on plan in need of revision.
|
BLD06-01538
| FIRE-Final Inspection | 4/28/2008 | 4/29/2008 | 4/29/2008 8:47:20 AM | A | FAIL |
|
|
Noted one smoke alarm at the second floor hallway unti 2173 that is not interconnected, unit 2175 is not ready for final life safety at this time due to condition of the project and missing smoke alarms not yet installed.
|