Inspections for the day of: Wednesday, April 29, 2009.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ESC08-00821 General Inspection4/29/20094/29/20094/29/2009 4:09:25 PMPPASS
looked ok
ESC09-00200 General Inspection4/29/20094/29/20094/29/2009 4:08:47 PMPPASS
looked ok, sign up
ESC08-00490 General Inspection4/29/20094/29/20094/29/2009 4:07:57 PMPPASS
looked ok
ESC08-00885 General Inspection4/29/20094/29/20094/29/2009 4:07:20 PMPPASS
looked ok
ELE08-02208 Final4/29/20094/29/20094/29/2009 4:06:35 PMPFAIL
Tom Phone #: ###-#### met contractor for roof top only, left correction notice, NEC 110.26(A)(2) shall provide at least 90 degree door opening for boiler controllers, 110.26(F)(1)shall provide dedicated space over controllers, with part (b) - nthere shall be no foreign piping over dedicated space, 400.8 shall not use so cord for fixed wiring, 408.4 shall provide circuit directories, 110.16 shall provide flash protection warning signs,200.6(A) shall identify grounded conductor, 110.22 shall identify disconnects
ELE09-00710 Electrical Rough-In4/29/20094/29/20094/29/2009 3:21:47 PMPPASS
jack - bonding Phone #: ###-#### pool bonding only ok, no u/g done
ELE06-04017 Final4/29/20094/29/20094/29/2009 2:42:57 PMPPASS
Michael Phone #: ###-#### ok to final, can't add esc response
ELE06-04017 Electrical Rough-In4/29/20094/29/20094/29/2009 2:06:57 PMPPASS
Michael Phone #: ###-#### corrections made, ric ok, can't add esc
ELE09-00672 Electrical Rough-In4/29/20094/29/20094/29/2009 1:59:11 PMPPASS
Mark Phone #: ###-#### called contractor, ric ok, no esc this project
ELE09-00518 Final4/29/20094/29/20094/29/2009 1:25:47 PMPPASS
Heath Phone #: ###-#### ok to final
ELE08-03176 Electrical Rough-In4/29/20094/29/20094/29/2009 10:52:21 AMAPASS
this is to relook at the ceiling for cover on the pendent lights Phone #: ###-#### Internet Inspection Request from: Don Lustig ok to cover rest of ceiling for pendant lights anop
ELE09-00719 Final4/28/20094/29/20094/29/2009 9:57:01 AMAPASS
Internet Inspection Request from: Daryl DeGrange ok to final, no esc this project
ELE09-00719 Temporary Service4/29/20094/29/20094/29/2009 9:56:47 AMAPASS
Internet Inspection Request from: Daryl DeGrange t/s u/g rec ok, no esc this project
ELE08-02256 Final4/28/20094/29/20094/29/2009 9:11:35 AMAPASS
Bryce- call 30 mins prior to going Phone #: ###-#### looked at kitchen receptacles, ok to final, no esc this project
ELE09-00248 Final4/28/20094/29/20094/29/2009 8:40:19 AMAPASS
Contact: Neil Ramsey Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok to final, no esc this project