Inspections for the day of: Wednesday, April 29, 2009.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00469 INSP-Final Inspection4/28/20094/29/20094/30/2009 3:58:58 PMPPASS
Permit finaled
FIR07-01032 INSP-Sprinkler Rough-in4/29/20094/29/20094/29/2009 3:39:49 PMPPASS
I went over sprinkler coverage under soffits in the second floor of the skilled nursing area. It appears that the placement of the pendant sprinkler heads will provide adequate coverage.
BLD08-02123 FIRE-Final Inspection4/29/20094/29/20094/29/2009 3:09:34 PMPFAIL
Provide panic hardware on the pool gates as per the city approved plans. Remove the chemicals from the storage room and blank the dead bolts on the restroom doors.
FIR08-00831 INSP-Sprinkler Rough-in/Hydro4/29/20094/29/20094/29/2009 3:08:14 PMPPASS
The first floor building "B" sprinkler piping can be covered.
BLD08-01210 FIRE-Final Inspection4/28/20094/29/20094/29/2009 2:54:28 PMAFAIL
This was actually a conference for the placement of the exterior electric alarm bell. Per mark sentenno the bell can be placed on the glass wall above the fdc or 15'-0" to the west, above the glass panels, in the rock wall.
FIR09-00016 FIR-Aging Inspection4/29/20094/29/20094/29/2009 12:19:28 PM NR
work in progress
FIR08-00832 INSP-Sprinkler Rough-in/Hydro4/28/20094/29/20094/29/2009 12:18:48 PMAPART
Todays inspection was for the third floor piping of building "C". The pipe size and hangers are passed. Another inspection will be required prior to cover for the insulation.
BLD09-00596 FIRE-Final Inspection4/28/20094/29/20094/29/2009 11:11:48 AMAPART
A temporary occupancy was given until the exit sign is repaired or removed, the sprinkler pendants that are too close together are addressed, the existing fire extinguisher is tagged with a current inspection tag and the dead bolt is removed from the rear exit door.
BLD09-00438 FIRE-Final Inspection4/28/20094/29/20094/29/2009 8:59:05 AMAPASS
Life safety passed. I noted that the existing stairwell door was missing the smoke seal and also the rating label on the door to the new coffee room has the rating hand written on it.
FIR09-00240 INSP-Final Inspection4/28/20094/29/20094/29/2009 8:01:26 AMAPASS
Permit finaled