Inspections for the day of: Thursday, April 29, 2010.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-00557 Final4/29/20104/29/20104/29/2010 3:54:01 PMPPASS
ok to final, signed card
ELE10-00918 Electrical Rough-In4/28/20104/29/20104/29/2010 3:53:24 PMPPASS
call ahead and I''ll meet you there to let you in. Inspection requested from web by: Andy Derrick Phone #: ###-#### ric ok, no esc
ELE10-00565 Electrical Rough-In4/29/20104/29/20104/29/2010 3:46:06 PMPPART
tyson Phone #: ###-#### ok to cover south walls only for steel beam installation
ELE10-00733 Final4/29/20104/29/20104/29/2010 3:33:53 PMPCANC
Contact Shane. Call before going to schedule for Shane to meet you there. Inspection requested from web by: Shelli Daylong Phone #: ###-#### Inspection cancelled from web by: Deb Gooden
ELE10-00557 Electrical Rough-In4/29/20104/29/20104/29/2010 2:51:39 PMPPASS
Inspection requested from web by: Mark M Phone #: ###-#### ric ok, no esc this project
ELE10-00904 Rough-In Permanent Service4/27/20104/29/20104/29/2010 2:21:07 PMPPASS
Inspection requested from web by: Daryl DeGrange Phone #: ###-#### ric ok, p/s u/g n ok
ELE10-00910 Rough-In Permanent Service4/28/20104/29/20104/29/2010 1:28:40 PMPPASS
This is a service change, if you have any questions, please give Clay a call. Inspection requested from web by: Clay Morgan Phone #: ###-#### ric ok, p/s u/g rec ok, no esc this project
GCE10-00049 GCE-Final4/28/20104/29/20104/29/2010 1:11:18 PMAFAIL
(Mandatory Inspection)Scope of inspection: FinalContact: Tim @ ###-####Customer will need A.M. inspection please called, left correction notice, NEC 250.64(C) gec shall only be spliced by irreversible connectors, 250.92 (B) shall bond service raceways, 210.5 shall identify conductors, 110.12(A) shall close unused openings in equipment, 350.30 shall secure fmc within 12" of termination, BCC 4-05-33(A)&(B) all equipment shall be listed by a nationally recognized testing laboratory, NOTE corrections shall be made within 10 working days or further action will be taken
GCE10-00012 GCE-Permanent Service4/28/20104/29/20104/29/2010 1:00:54 PMACANC
Scope of inspection: Permanent ServiceContact: Mike @ ###-#### built scaffolding in front of panel, told to recall for am inspection
ELE10-00512 Final4/28/20104/29/20104/29/2010 11:44:18 AMAFAIL
Inspection requested from web by: Therrin Robertson Phone #: ###-#### called, left correction notice, NEC 210.8(A)(3) front receptacle shall be gfci protected
ELE10-00862 Final4/27/20104/29/20104/29/2010 9:59:57 AMAPASS
Inspection requested from web by: Stuart Welton ok to final, no esc this project
ELE10-00552 Final4/28/20104/29/20104/29/2010 9:46:19 AMAPASS
BILL Inspection requested from web by: Bob Glenn Phone #: ###-#### ok to final
ELE10-00912 Final4/28/20104/29/20104/29/2010 9:05:55 AMACANC
Inspection requested from web by: Zane Robertson Phone #: ###-#### wrong type request, see t/s
ELE10-00912 Temporary Service4/29/20104/29/20104/29/2010 8:57:35 AMAPASS
Inspection requested from web by: Zane Robertson Phone #: ###-#### called, t/s u/g n ok
ELE10-00477 Final4/28/20104/29/20104/29/2010 8:52:26 AMAPASS
Inspection requested from web by: Barbara Szurgot Phone #: ###-#### ok to final, signed card, no esc this project
ELE10-00920 Final4/29/20104/29/20104/29/2010 8:04:48 AMACANC
call mike with any questions. thanks Inspection requested from web by: mike brown Phone #: ###-#### wrong type request, see t/s
ELE10-00920 Temporary Service4/29/20104/29/20104/29/2010 8:04:28 AMAPASS
call mike with any questions. thanks Inspection requested from web by: mike brown Phone #: ###-#### t/s u/g n ok
ELE10-00910 Final4/28/20104/29/20104/28/2010 3:34:36 PMPCANC
Any questions, please give Clay a call, thank you. Inspection requested from web by: Clay Morgan Phone #: ###-#### (Disaster Kleenup came in and spoke to Perry. Said they are replacing all sheetrock and reinsulating in garage and replaceing garage door. Perry said no building permit required//4/28/10 leg) Inspection cancelled from web by: Clay Morgan