FIR10-00033
| FIR-Aging Inspection | 4/29/2010 | 4/29/2010 | 4/30/2010 2:16:31 PM | | NR |
|
|
Per Mark this project is acouple of months off due to the elevator being re-built.
|
BLD09-01495
| FIRE-Final Inspection | 4/29/2010 | 4/29/2010 | 4/29/2010 3:52:33 PM | P | FAIL |
|
|
All items except for the repair/addition of exit signs and emergency lights as discussed have been corrected.
|
BLD09-01275
| FIRE-Final Inspection | 4/28/2010 | 4/29/2010 | 4/29/2010 3:49:44 PM | P | FAIL |
|
|
The project related fire alarm permit needs to be finaled. Also indicators and stickers need to be installed at the two sets of double main entry doors. The exit discharge light on the northwest exit door did not function.
|
FIR09-00551
| INSP-Final Inspection | 4/28/2010 | 4/29/2010 | 4/29/2010 3:45:13 PM | P | FAIL |
|
|
All items have been corrected. The hvac units had not been programmed yet so shut down could not be tested. The hvac installer needs to provide verification that the smoke duct detectors are factory installed or per System Sensor tech support the sample tubes will need to extend 2/3 of the way across the duct. As installed they do not.
|
FIR10-00014
| INSP-Final Inspection | 4/28/2010 | 4/29/2010 | 4/29/2010 3:36:17 PM | P | PASS |
|
|
Permit finaled
|
BLD10-00203
| FIRE-Final Inspection | 4/29/2010 | 4/29/2010 | 4/29/2010 3:35:52 PM | P | FAIL |
|
|
Provide annual inspection for the new fire extinguisher and repair the rear exit sign/emergency light which includes the exsit discharge light.
|
FIR10-00018
| INSP-Final Inspection | 4/28/2010 | 4/29/2010 | 4/29/2010 3:21:53 PM | P | PASS |
|
|
Permit finaled
|
BLD08-00225
| FIRE-Final Inspection | 4/28/2010 | 4/29/2010 | 4/29/2010 1:21:12 PM | P | PASS |
|
|
Life safety passed
|
FIR09-00681
| INSP-Final Inspection | 4/28/2010 | 4/29/2010 | 4/29/2010 1:20:30 PM | P | PASS |
|
|
Permit finaled
|
FIR09-00269
| INSP-Final Inspection | 4/29/2010 | 4/29/2010 | 4/29/2010 11:51:01 AM | P | PASS |
|
|
Permit finaled. The netcon was a 5.
|
FIR10-00147
| INSP-Sprinkler Rough-in | 4/28/2010 | 4/29/2010 | 4/29/2010 10:08:30 AM | A | PASS |
|
|
All of the sprinkler piping located above the hard lids is ok for cover. I spoke to Rick and also the general contractor about possible additional sprinkler work in the corridor being built to the north of the new tenant.
|
BLD10-00360
| FIRE-Final Inspection | 4/28/2010 | 4/29/2010 | 4/29/2010 10:00:05 AM | A | PASS |
|
|
life safety passed
|
FIR10-00138
| INSP-Final Inspection | 4/29/2010 | 4/29/2010 | 4/29/2010 9:59:45 AM | P | PASS |
|
|
permit finaled
|