Inspections for the day of: Thursday, April 29, 2010.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00033 FIR-Aging Inspection4/29/20104/29/20104/30/2010 2:16:31 PM NR
Per Mark this project is acouple of months off due to the elevator being re-built.
BLD09-01495 FIRE-Final Inspection4/29/20104/29/20104/29/2010 3:52:33 PMPFAIL
All items except for the repair/addition of exit signs and emergency lights as discussed have been corrected.
BLD09-01275 FIRE-Final Inspection4/28/20104/29/20104/29/2010 3:49:44 PMPFAIL
The project related fire alarm permit needs to be finaled. Also indicators and stickers need to be installed at the two sets of double main entry doors. The exit discharge light on the northwest exit door did not function.
FIR09-00551 INSP-Final Inspection4/28/20104/29/20104/29/2010 3:45:13 PMPFAIL
All items have been corrected. The hvac units had not been programmed yet so shut down could not be tested. The hvac installer needs to provide verification that the smoke duct detectors are factory installed or per System Sensor tech support the sample tubes will need to extend 2/3 of the way across the duct. As installed they do not.
FIR10-00014 INSP-Final Inspection4/28/20104/29/20104/29/2010 3:36:17 PMPPASS
Permit finaled
BLD10-00203 FIRE-Final Inspection4/29/20104/29/20104/29/2010 3:35:52 PMPFAIL
Provide annual inspection for the new fire extinguisher and repair the rear exit sign/emergency light which includes the exsit discharge light.
FIR10-00018 INSP-Final Inspection4/28/20104/29/20104/29/2010 3:21:53 PMPPASS
Permit finaled
BLD08-00225 FIRE-Final Inspection4/28/20104/29/20104/29/2010 1:21:12 PMPPASS
Life safety passed
FIR09-00681 INSP-Final Inspection4/28/20104/29/20104/29/2010 1:20:30 PMPPASS
Permit finaled
FIR09-00269 INSP-Final Inspection4/29/20104/29/20104/29/2010 11:51:01 AMPPASS
Permit finaled. The netcon was a 5.
FIR10-00147 INSP-Sprinkler Rough-in4/28/20104/29/20104/29/2010 10:08:30 AMAPASS
All of the sprinkler piping located above the hard lids is ok for cover. I spoke to Rick and also the general contractor about possible additional sprinkler work in the corridor being built to the north of the new tenant.
BLD10-00360 FIRE-Final Inspection4/28/20104/29/20104/29/2010 10:00:05 AMAPASS
life safety passed
FIR10-00138 INSP-Final Inspection4/29/20104/29/20104/29/2010 9:59:45 AMPPASS
permit finaled