Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-00861 FIRE-Final Inspection4/25/20134/29/20134/29/2013 3:58:32 PMPCANC
Hood suppression system is not ready yet. To be rescheduled. kana Phone #: ###-####
FIR13-00095 INSP-Sprinkler Rough-in/Hydro4/29/20134/29/20134/29/2013 3:53:28 PMPFAIL
Due to extensive routing modifications, swing joints and additional sprinkler heads plan modifications will be needed for this project. Don is going to provide verification the pipe straps and screws are listed for hanging the 2" mains. Siesmic restraints are required for the branchlines. There is wood at the top of the old fire place so sprinkler protection as per the plans will be required. There appears to be an addtional combustible concealed space near the kitchen that will need sprinkler protection.
FIR13-00141 INSP-Final Inspection4/28/20134/29/20134/29/2013 3:44:35 PMPFAIL
The hvac unit in the second floor sewing room failed to shutdown when the duct smoke detector was activated. The flow switch alarms do not latch as required and the outside electric alarm bell did not function. Per Robert the 5 year elevator inspection is going to require the fire mans hat to function correctly. He would like to waite until this elevator work is complete prior to testing/finaling this permit.
BLD12-02551 FIRE-Final Inspection4/26/20134/29/20134/29/2013 3:39:50 PMAFAIL
No city approved plans/notes on site. I went over general life safety requirements with the builder. He currently has thumbturn deadbolts on all doors which will probably be an issue. Also needs address.
BLD12-02376 FIRE-Final Inspection4/26/20134/29/20134/29/2013 3:37:16 PMAPASS
life safety passed. Door #2, west facing door, per the plans is required to have panice hardware. Before the building inspection the door is to be provided with the approved hardware or the keyed hardware needs to be approved by plan review.
BLD12-03181 FIRE-Final Inspection4/26/20134/29/20134/29/2013 10:20:19 AMAPASS
life safety passed