ELE13-02432
| ELE-Aging Inspection | 4/29/2016 | 4/29/2016 | 4/29/2016 4:19:14 PM | | CANC |
|
|
|
ELE12-02127
| ELE-Aging Inspection | 4/29/2016 | 4/29/2016 | 4/29/2016 4:18:40 PM | | CANC |
|
|
|
ELE12-00814
| ELE-Aging Inspection | 4/29/2016 | 4/29/2016 | 4/29/2016 4:17:48 PM | | CANC |
|
|
|
ELE16-01174
| Conference | 4/29/2016 | 4/29/2016 | 4/29/2016 4:13:54 PM | P | DONE |
|
|
Zahid Phone #: ###-#### discussed wiring to shed, 30amp feed for welder and light and receptacle. Conduit pre installed under driveway OK will dig to 18" as soon as possible after leaving concrete and maintain depth to shed. GFCI protection of receptacles and disconnect on interior of shed in wall OK. Need to remind of tamper
|
ELE16-01360
| Conference | 4/29/2016 | 4/29/2016 | 4/29/2016 3:39:00 PM | P | DONE |
|
|
Steve-please call 30 m inutes prior to meet Phone #: ###-#### Discussed the addition of hot tub. 2800 sq. ft house needs service change to larger service to add hot tub. Bond gutter and fence post near tub location.
|
ELE15-04022
| Final | 4/27/2016 | 4/29/2016 | 4/29/2016 2:37:55 PM | P | FAIL |
|
|
Jake is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates 250.30- Common neutral bar and transfer switch, non seperately derived system, Seperate grounds and neutral at generator.
|
ELE14-00519
| ELE-Request for Extension | 4/29/2016 | 4/29/2016 | 4/29/2016 12:57:40 PM | P | PASS |
|
|
Clark// please call before Phone #: ###-#### Still under construction. Extension OK
|
ELE16-00801
| Electrical Rough-In | 4/28/2016 | 4/29/2016 | 4/29/2016 12:49:58 PM | P | FAIL |
|
|
Tile floor heat Phone #: ###-#### Inspection requested via web by danny perrine 110.3- Floor heat cable shall be installed as per manufacturers instructions. Cold lead splice shall be enbedded in tile floor.
|
ELE16-01314
| Permanent Service | 4/29/2016 | 4/29/2016 | 4/29/2016 12:20:12 PM | P | PASS |
|
|
Service energize inspection Phone #: ###-#### Inspection requested via web by April Brown p/s u/g n ok
|
ELE16-01148
| Final | 4/29/2016 | 4/29/2016 | 4/29/2016 11:33:34 AM | A | PASS |
|
|
For access please call Richie 1/2 hr prior to inspection.###-#### Inspection requested via web by Terry Scott Final ok
|
ELE16-00868
| Final | 4/29/2016 | 4/29/2016 | 4/29/2016 11:20:46 AM | A | PASS |
|
|
Daven Story on site. Phone #: ###-#### Inspection requested via web by Brian Caruso Final ok
|
ELE16-01357
| Final | 4/28/2016 | 4/29/2016 | 4/29/2016 10:56:03 AM | A | FAIL |
|
|
I put the address in as 915 S Curtis Rd and it should be 815 S Curtis Rd - Trlr 71 Boise, id - If you have any questions , please call David Kubik - ###-#### Phone #: ###-#### Inspection requested via web by Charmel Kubik 230.28- Overhead service pole strength. Base of pole has rotte out and needs to be replaced. Make sure drip loop is min of 10' above grade. 362.48- ENT joists shall be of as approved method. ENT to PVC TA joint duct taped. 352.30- PVC conduit shall be secured in place under trailer. Call and correct address
|
ELE16-00866
| Final | 4/28/2016 | 4/29/2016 | 4/29/2016 8:25:37 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
ELE16-01357
| Final | 4/28/2016 | 4/29/2016 | 4/28/2016 8:45:59 PM | A | CANC |
|
|
Please call David Kubik - ###-#### if there is any questions Phone #: ###-#### >> Inspection requested via web by Charmel Kubik Inspection cancelled from web by: Charmel Kubik
|