BLD16-00541
| FIRE-Final Inspection | 4/28/2016 | 4/29/2016 | 4/29/2016 2:09:04 PM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguisher is on site, discussed with point of contact an acceptable location for extinguisher mount. Final life fire safety inspection complete.
|
BLD15-02706
| FIRE-Final Inspection | 4/29/2016 | 4/29/2016 | 4/29/2016 11:43:02 AM | P | PASS |
|
|
No fire alarms, one fire sprinkler located in compressed gas closet (Not associated with an FIR permit, sprinkler head is supplied by domestic water) fire extinguishers in place with current inspection tags. Thumb-turn deadbolt hardware on interior records room door will be removed. Final life fire safety inspection passed/complete.
|
BLD15-02657
| FIRE-Final Inspection | 4/28/2016 | 4/29/2016 | 4/29/2016 10:43:26 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are in place with current inspections, exit signs/egress lighting/discharge landing lighting verfied, all operated correctly. Final life fire safety inspection passed/complete.
|
BLD15-02530
| FIRE-Final Inspection | 4/28/2016 | 4/29/2016 | 4/29/2016 10:42:53 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are in place with current inspections, exit signs/egress lighting/discharge landing lighting verfied, all operated correctly. Final life fire safety inspection passed/complete.
|
FIR16-00106
| INSP-Sprinkler Rough-in/Hydro | 4/28/2016 | 4/29/2016 | 4/29/2016 10:11:37 AM | A | PASS |
|
|
200 psi hydrostatic test for overhead fire sprinkler piping complete. Rough in inspection for shell protection complete, end of line sway bracing was not installed at time of inspection, end of line sway bracing install will be verified at final fire sprinkler inspection.
|
FIR15-00806
| INSP-Sprinkler Rough-in | 4/28/2016 | 4/29/2016 | 4/29/2016 10:03:08 AM | P | PART |
|
|
200 psi hydrostatic test complete for level three, this completes the hydrostatic testing for this building. Rough in inspection complete for level 3, tenting insulation for overhead fire sprinkler piping, north of the fire doors complete. Hardlids north of the fire doors approved for cover. Remaining cover inspection for overhead fire sprinkler tenting south of the fire doors will be scheduled when insulation install is complete.
|
FIR16-00017
| INSP-Sprinkler Rough-in/Hydro | 4/25/2016 | 4/29/2016 | 4/28/2016 11:46:01 AM | P | CANC |
|
|
Please call when you are headed out. Thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|