ELE02-00749
| Electrical Rough-In | 4/2/2002 | 4/3/2002 | 4/3/2002 12:00:00 AM | A | FAIL |
|
|
R/I FOR A/C-- BRIAN- ###-#### cor. posted,called 110.14 use listed devices to splice copper and alum 314.17 use con. for romex bell box 314.22 secure box extension and grd as 250 states 110.14(A) terminate wires in device 4/3/2002 11:39:19 AM
|
ELE02-00340
| Final | 4/2/2002 | 4/3/2002 | 4/3/2002 12:00:00 AM | A | PASS |
|
|
ALLEN ###-#### RE-INSP FN --FOR ACCESS TO GAR 0256 ENTER ok 4/3/2002 10:37:13 AM
|
ELE02-00303
| Final | 4/3/2002 | 4/3/2002 | 4/3/2002 12:00:00 AM | P | PASS |
|
|
fn -patrick ###-#### OK 4/3/2002 4:23:06 PM
|
ELE02-00916
| Electrical Rough-In | 4/3/2002 | 4/3/2002 | 4/3/2002 12:00:00 AM | P | PART |
|
|
conference only marv ###-#### conference ok cor. posted for contractor and red tag posted for owner see JF for details 4/3/2002 1:29:50 PM
|
ELE02-00625
| Rough-In Permanent Service | 4/3/2002 | 4/3/2002 | 4/3/2002 12:00:00 AM | P | FAIL |
|
|
###-#### metcalf NOT READY CALLED 4/3/2002 5:05:20 PM
|
ELE02-00871
| Permanent Service | 4/3/2002 | 4/3/2002 | 4/3/2002 12:00:00 AM | P | FAIL |
|
|
###-#### - no access called no cor. posted could not do complete inspection no access inside job site $42.00 fee due 4/3/2002 3:50:52 PM
|
ELE02-00904
| Permanent Service | 4/3/2002 | 4/3/2002 | 4/3/2002 12:00:00 AM | P | FAIL |
|
|
for an emmission test van--allison- ###-#### cor. posted called 250.24 shall terminate
GEC to grounded conductor at p/s useing manufactures means there is no connection between at time of inspection 4/3/2002 2:33:09 PM
|