FIR05-00659
| INSP-Final Inspection | 3/30/2006 | 4/3/2006 | 4/4/2006 11:53:08 AM | A | DEFR |
|
|
Inspection rescheduled.
|
BLD05-01346
| FIRE-Final Inspection | 4/3/2006 | 4/3/2006 | 4/3/2006 3:39:37 PM | P | NR |
|
|
The project related fire alarm permit must be finaled previous to a building life safety inspection for final.
|
FIR06-00227
| INSP-Final Inspection | 4/3/2006 | 4/3/2006 | 4/3/2006 3:06:40 PM | P | PASS |
|
|
Fire sprinkler work is satisfactory.
|
BLD04-00949
| FIRE-Final Inspection | 4/3/2006 | 4/3/2006 | 4/3/2006 3:04:20 PM | P | NR |
|
|
Project does not appear to have an attatched fire alarm permit as required. Fire alarm work must be inspected and approved prior to building life safety final.
|
BLD06-00084
| FIRE-Final Inspection | 4/3/2006 | 4/3/2006 | 4/3/2006 2:57:46 PM | P | NR |
|
|
Door hardware at two locations is not installed yet, missing fire sprinkler escutcheon at closet, need to post max. occupant load sign as discussed, ceiling tile is not installed at relocated heads.
|
FIR06-00073
| INSP-Supply line flush | 3/31/2006 | 4/3/2006 | 4/3/2006 12:16:21 PM | A | PART |
|
|
UG fire supply line flush performed satisfactory.
|
FIR05-00405
| INSP-Final Inspection | 3/31/2006 | 4/3/2006 | 4/3/2006 11:30:25 AM | A | PART |
|
|
Heads blocked by surface mounted lights have been moved, some escutcheons are not installed, performed forward flow, final pending testing of sprinkler related alarms and supervisory conditions.
|
BLD05-03349
| FIRE-Final Inspection | 3/31/2006 | 4/3/2006 | 4/3/2006 9:51:49 AM | A | FAIL |
|
|
Two exit signs failed to illuminate under battery backup, the exit discharge light at exit facing State street is missing a lamp, need to install and test.
|