Inspections for the day of: Monday, April 3, 2006.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00083 INSP-Final Inspection4/3/20064/3/20064/3/2006 4:07:32 PMPNR
low air pressure switch has not been setup. no items tested except hood which tested ok
FIR05-00869 INSP-Final Inspection4/3/20064/3/20064/3/2006 3:50:08 PMPFAIL
manual pull needs to be located more than 10' but less 20'. Hood suppression system operated correctly
FIR05-00898 INSP-Final Inspection3/31/20064/3/20064/3/2006 1:27:00 PMAFAIL
Zones 2 and 6 are reported as troubles but should be supervisory since they are tamper switches.