FIR06-00083
| INSP-Final Inspection | 4/3/2006 | 4/3/2006 | 4/3/2006 4:07:32 PM | P | NR |
|
|
low air pressure switch has not been setup. no items tested except hood which tested ok
|
FIR05-00869
| INSP-Final Inspection | 4/3/2006 | 4/3/2006 | 4/3/2006 3:50:08 PM | P | FAIL |
|
|
manual pull needs to be located more than 10' but less 20'. Hood suppression system operated correctly
|
FIR05-00898
| INSP-Final Inspection | 3/31/2006 | 4/3/2006 | 4/3/2006 1:27:00 PM | A | FAIL |
|
|
Zones 2 and 6 are reported as troubles but should be supervisory since they are tamper switches.
|