Inspections for the day of: Tuesday, April 3, 2007.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-00246 Rough-In Permanent Service4/3/20074/3/20074/3/2007 4:34:20 PMPFAIL
CONTACT JACK Phone #: ###-####
corr. called left message 300.4 nail plates 11/4" for cables, 250.68 provide access panel for acorn at rebar
ELE07-00244 Rough-In Permanent Service4/3/20074/3/20074/3/2007 4:32:59 PMPFAIL
CONTACT JACK Phone #: ###-####
corr. called 300.4 nail plates and 11/4" for cables, 250.68 provide access panel for acorn at rebar
ELE07-00739 Final4/3/20074/3/20074/3/2007 3:31:33 PMPFAIL
Phone #: ###-#### corr. called shall provide access to panel rm, provide dual level switcher as bld permit states, seal all unused openings, install all end caps, fittings, etc. for offic cubicals
ELE07-01024 Electrical Rough-In4/3/20074/3/20074/3/2007 2:32:01 PMPPART
Scheduled by a contractor via Hello! on 4/3/2007 at 7:33:57 AM. Contact: ###-####. walls ok
ELE07-01023 Electrical Rough-In4/3/20074/3/20074/3/2007 2:11:09 PMPPART
Scheduled by a contractor via Hello! on 4/3/2007 at 7:35:35 AM. Contact: ###-####. walls ok
ELE07-00833 Electrical Rough-In4/3/20074/3/20074/3/2007 1:28:29 PMPPASS
zac; Phone #: ###-#### Internet Inspection Request from: Victoria Beall r/i ok
ELE07-01077 Permanent Service4/3/20074/3/20074/3/2007 11:58:36 AMPPASS
###-#### p/s u/g rec. for meter ok space 100
ELE07-00762 Rough-In Permanent Service4/2/20074/3/20074/3/2007 9:53:31 AMANR
On site journeyman, Gene - ###-####
Thank You Phone #: ###-####
see added p/s, r/i not ready tin benders messed up wiring
ELE07-00762 Permanent Service4/3/20074/3/20074/3/2007 9:52:27 AMAPASS
On site journeyman, Gene - ###-####
Thank You Phone #: ###-####
p/s u/g new ok
ELE07-00070 Final4/3/20074/3/20074/3/2007 9:08:01 AMAPASS
Scheduled by a contractor via Hello! on 4/3/2007 at 7:01:39 AM. Contact: (208)
ok corrections made
ELE07-01085 Temporary Service4/2/20074/3/20074/3/2007 8:42:02 AMAPASS
daryl; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
t/s o/h new ok
ELE07-01069 Temporary Service4/3/20074/3/20074/3/2007 8:26:33 AMAPASS
the address on the erosion control was wrong this the right address Phone #: ###-#### t/s u/g new ok
ELE06-00363 Final4/2/20074/3/20074/3/2007 8:10:16 AMAPASS
todd; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok