Inspections for the day of: Tuesday, April 3, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Johnson
TitlePLM-INSPECTOR
Phone #794-9476
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
PLM07-00921 Groundwork4/3/20074/3/20074/3/2007 3:56:01 PMPNR
THE INSPECTION IS A PARTIAL. JOB CONTACT IS RANDY R Phone #: ###-#### not ready
PLM06-03191 Final4/3/20074/3/20074/3/2007 3:22:03 PMPPART
Phone #: ###-#### need to repipe water supply to eye wash in garage bay area on the upstream side of R.P. need to have PVB on eye wash tested and certified need non potable water sign on water supply to swamp cooler oked temp
PLM07-00967 Plumbing Rough-in4/2/20074/3/20074/3/2007 2:33:39 PMPCANC
Phone #: ###-#### canc by Gary
PLM07-00388 Final4/3/20074/3/20074/3/2007 2:32:58 PMPPASS
PLM07-00942 Final3/29/20074/3/20074/3/2007 2:32:13 PMPNH
troy ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith not home no access
PLM07-00966 Water and/or Sewer4/2/20074/3/20074/3/2007 1:38:19 PMPPART
tom; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles sewer line only test ok ok to cover
PLM06-03987 Final4/2/20074/3/20074/3/2007 1:16:05 PMAPASS
tim; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
PLM05-04309 Plumbing Rough-in4/2/20074/3/20074/3/2007 12:49:27 PMAPART
Scheduled by a contractor via Hello! on 4/2/2007 at 11:31:58 AM. 6th floor under floor DWV rough-in on south east , east , and north east side of building
PLM06-01181 Plumbing Rough-in4/2/20074/3/20074/3/2007 10:39:13 AMAPASS
rick; Phone #: ###-#### Internet Inspection Request from: Victoria Beall rerouhj-in test ok ok to cover
PLM07-00573 Med/Gas Systems4/2/20074/3/20074/3/2007 10:13:55 AMAFAIL
Please call Jim with any questions ###-#### Phone #: ###-#### x238 under ground med gas piping with in building need to be installed under following conditions noted in NFPA 99 C 2002 edition section 5.3.10.10.7 through 5.3.10.10.7.4 contractor to recall when ready
PLM07-00388 Final4/2/20074/3/20074/3/2007 9:09:39 AMANR
JOB CONTACT: JAYSON T Phone #: ###-#### not ready